Product Certifications
Standards: C22.2 NO. 0.4-04:2004 (R2013), C22.2 NO. 0.5-16:2016, C22.2 No.
Markings:
Specific Conditions of Use (X):
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
(3) Other temperature ranges may apply, see Specific Conditions of Use (X).
200
25-1966:1966 (R:2014), C22.2 No.30-M1986:1986 (R:2012), C22.2 No.94-
M91:1991 (R:2011), C22.2 No. 1010.1:2004, CAN/CSA C22.2 No.
60079-0:2015 Ed. 3, C22.2 No. 60079-1:2016 Ed. 3, C22.2 No.
60079-26:2016; CAN/CSA-C22.2 No. 60079-31:2015, C22.2. 60529:2005
(R:2015), ANSI/ISA 12.27.01:2011
XP CL I, DIV 1, GRPS A-D T6...T2
DIP CLII/III, DIV 1, GRPS E-G; T6...T3
Ex db IIC T6...T3 Gb
Ex tb IIIC T85 °C...T250°C Db
(-40°C ≤ Ta ≤ +70°C)
SINGLE SEAL
Flamepath joints are not for repair. Contact the manufacturer.
Plastic wire-on tag, Plastic part of Process Seal Antenna and Non-standard paint
options (paint options other than Rosemount Blue) may cause risk from
Electrostatic discharge. Avoid installation that could cause electrostatic build-up,
and only clean with a damp cloth.
Appropriate cable, glands, and plugs need to be suitable for a temperature of 5°C
greater than the maximum specified ambient temperature for location where
installed.
Metric Field Wiring Entries are not allowed for Divisions.
The Transmitter can be installed in the boundary wall between a Zone 0 and Zone 1
area. In this configuration, the process connection is installed in Zone 0, while the
transmitter housing is installed in Zone 1. Refer to Control Drawing D7000002-885.
Cable entries must be used which maintain the ingress protection of the enclosure
to at least IP6X and/or Type 4X rating. To maintain the ingress protection ratings.
Covers and Sensor Module to be fully tightened and PTFE tape or pipe dope is
required for cable entries and blanking plugs. See Instruction Manual on application
requirements.
Install per Control Drawing D7000002-885.
Using the box provided on the nameplate, the User shall permanently mark the type
of protection chosen for the specific installation. Once the type of protection has
been marked it shall not be changed.
Display glass shall be positioned in such a way as to minimize the risk of mechanical
impact.
The applicable temperature class, ambient temperature range and process
temperature range of the equipment is as follows;
(3)
; Type 4X/IP6X
Reference Manual