Service and Troubleshooting
Table 7-1:
Status - Failed
LCD display
Host diagnostic mes-
message
sage
ELEC FAILUR
Electronics Failure,
Transmitter
ELEC FAILUR
Electronics Failure, Sen-
sor Module
MEMRY FAILUR
Device Memory Failure
SIGNL FAILUR
Radar Signal Failure
START FAILUR
Startup Failure
SW ERROR
Software Error
86
Description
An electronics error has occurred.
The device measurement reading is
invalid.
An electronics error has occurred.
The device measurement reading is
invalid.
A device memory error has occur-
red.
The device measurement reading is
invalid.
The received radar signal is invalid
resulting in an invalid device meas-
urement reading.
Device repeatedly failed to start up
with user configuration settings.
The device measurement reading is
invalid.
The software in the device encoun-
tered a problem and stopped run-
ning which may cause an invalid
measurement reading.
In some cases, problems may be
caused by temporary environmen-
tal conditions (e.g. electromagnetic
interferences) and not observed
again.
Recommended actions
1. Restart the device.
2. If the condition persists, replace
the device.
1. Restart the device.
2. If the condition persists, replace
the device.
1. Restore default settings, restart
device, and reconfigure the de-
vice.
2. If the condition persists, replace
the device.
1. Clean the antenna.
2. If the condition persists, replace
the device.
1. Check supply voltage is within
range and restart device.
2. Restore default settings, restart
device, and reconfigure the de-
vice.
3. If the condition persists, replace
the device.
1. Restart the device.
2. Restore default settings and re-
configure the device.
3. If the condition persists, replace
the device.
Reference Manual