6 Parameter Table
No.
Name
0: Disabled. Deceleration at the active
deceleration rate. An ov fault may occur.
1: General purpose. Deceleration is
paused when the DC bus voltage exceeds
the Stall Prevention level.
2: Intelligent. Decelerate as fast as possible
while avoiding ov faults.
Stall
3: Stall Prevention with braking resistor.
Prevention
Stall Prevention during deceleration is
L3-04
Selection
enabled in coordination with dynamic
during
braking.
Deceleration
4: Overexcitation Deceleration. Decelerates
while increasing the motor flux.
5: Overexcitation Deceleration 2. Adjust the
deceleration rate according to the DC bus
voltage.
6: Enabled. Decelerates adjusting the
deceleration rate according to the output
current and the DC bus voltage.
0: Disabled. Drive runs at a set frequency. A
heavy load may cause speed loss.
Stall
1: Decel time 1. Uses the deceleration
Prevention
time set to C1-02 while Stall Prevention is
L3-05
Selection
performed.
during Run
2: Decel time 2. Uses the deceleration time
set to C1-04 while Stall Prevention is
performed.
Stall
Prevention
Enabled when L3-05 is set to 1 or 2. 100%
L3-06
Level during
is equal to the drive rated current.
Run
Induction Motor Auto-Tuning
0: Rotational Auto-Tuning
1: Stationary Auto-Tuning 1
2: Stationary Auto-Tuning for Line-to-Line
Resistance
3: Rotational Auto-Tuning for V/f Control
Auto-Tuning
(necessary for Energy Savings and Speed
T1-01
Mode
Estimation Speed Search)
Selection
4: Stationary Auto-Tuning 2
8: Inertia Tuning (perform Rotational Auto-
Tuning prior to Inertia Tuning)
9: ASR Gain Tuning (perform Rotational
Auto-Tuning prior to ASR Gain Auto-
Tuning)
Motor Rated
Sets the motor rated power as specified on
T1-02
Power
the motor nameplate.
Motor Rated
Sets the motor rated voltage as specified on
T1-03
Voltage
the motor nameplate.
Motor Rated
Sets the motor rated current as specified on
T1-04
Current
the motor nameplate.
Motor Base
Sets the rated frequency of the motor as
T1-05
Frequency
specified on the motor nameplate.
Number of
Sets the number of motor poles as specified
T1-06
Motor Poles
on the motor nameplate.
Motor Base
Sets the rated speed of the motor as
T1-07
Speed
specified on the motor nameplate.
PG Number of
Set the number of pulses per revolution for
T1-08
Pulses Per
the PG being used (pulse generator or
Revolution
encoder).
EN 32
Description
YASKAWA Europe TOEP C710616 88A - AC Drive A1000 IP23/54 Floor Standing - Quick Start Guide
No.
Name
Sets the no-load current for the motor.
After setting the motor capacity to T1-02
Motor No-
and the motor rated current to T1-04, this
Load Current
T1-09
parameter will automatically display the no-
(Stationary
load current for a standard 4 pole
Auto-Tuning)
YASKAWA motor. Enter the no-load
current as indicated on the motor test report.
Sets the motor rated slip.
Motor Rated
After setting the motor capacity to T1-02,
Slip
this parameter will automatically display the
T1-10
(Stationary
motor slip for a standard 4 pole YASKAWA
Auto-Tuning)
motor. Enter the motor slip as indicated on
the motor test report.
Sets the iron loss for determining the
Energy Saving coefficient.
Motor Iron
The value is set to E2-10 (motor iron loss)
T1-11
Loss
set when the power is cycled. If T1-02 is
changed, a default value appropriate for the
motor capacity that was entered will appear.
Description