6 Parameter Table
No.
Name
1: 2.0 kHz
2: 5.0 kHz
3: 8.0 kHz
4: 10.0 kHz
5: 12.5 kHz
Carrier
6: 15.0 kHz
C6-02
Frequency
7: Swing PWM1 (Audible sound 1)
Selection
8: Swing PWM2 (Audible sound 2)
9: Swing PWM3 (Audible sound 3)
A: Swing PWM4 (Audible sound 4)
B to E: No setting possible
F: User defined (determined by C6-03
through C6-05)
Frequency Reference
Frequency
Sets the frequency reference for the drive.
d1-01 to
Reference
Setting units are determined by parameter
d1-16
1 to 16
o1-03.
Jog Frequency
Sets the Jog frequency reference. Setting
d1-17
Reference
units are determined by parameter o1-03.
V/f Pattern for Motor 1
This parameter must be set to the power
supply voltage.
WARNING! Drive input voltage (not motor
Input Voltage
voltage) must be set in E1-01 for the
E1-01
Setting
protective features of the drive to function
properly. Failure to do so may result in
equipment damage and/or death or personal
injury.
Maximum
These parameters are only applicable when
E1-04
Output
E1-03 is set to F.
Frequency
To set linear V/f characteristics, set the
same values for E1-07 and E1-09. In this
Maximum
E1-05
case, the setting for E1-08 will be
Voltage
disregarded. Ensure that the four
Base
E1-06
frequencies are set according to these rules:
Frequency
E1-09  E1-07  E1-06 E1-04
Middle Output
E1-07
Frequency
Middle Output
E1-08
Frequency
Voltage
Minimum
E1-09
Output
Frequency
Minimum
Output
E1-10
Note: Some parameters may not be
Frequency
available depending on the control mode.
Voltage
• E1-07, E1-08 and E-10 are available only
• E1-11, E1-12 and E-13 are available only
E1-13
Base Voltage
Motor 1 Parameters
Sets the motor nameplate full load current in
Motor Rated
E2-01
Amps. Automatically set during
Current
Auto-Tuning.
Motor Rated
Sets the motor rated slip. Automatically set
E2-02
Slip
during Auto-Tuning.
EN 30
Description
Output Voltage (V)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
E1-07 E1-06 E1-11 E1-04
Frequency (Hz)
in the following control modes: V/f
Control, V/f with PG, Open Loop Vector.
in the following control modes: V/f
Control, V/f with PG, Open Loop Vector,
Closed Loop Vector.
YASKAWA Europe TOEP C710616 88A - AC Drive A1000 IP23/54 Floor Standing - Quick Start Guide
No.
Name
Motor
Sets the no-load current for the motor.
E2-03
No-Load
Automatically set during Auto-Tuning.
Current
Number of
Sets the number of motor poles.
E2-04
Motor Poles
Automatically set during Auto-Tuning.
Motor
Sets the phase-to-phase motor resistance.
E2-05
Line-to-Line
Automatically set during Auto-Tuning.
Resistance
Sets the voltage drop due to motor leakage
Motor Leakage
inductance as a percentage of motor rated
E2-06
Inductance
voltage. Automatically set during
Auto-Tuning.
Multi-Function Digital Inputs
Multi-Function
Digital Input
Selects the function of terminals S1 to S8.
H1-01 to
Terminal S1 to
Setting H1-03 = 24 (Default) must not be
H1-08
S8 Function
changed. Fan monitoring function.
Selection
Note: Major functions are listed at the end of the table.
Multi-Function Digital Outputs
Terminal M1-
Set the function for the relay output M1-
H2-01
M2 function
M2.
selection
Terminal M3-
Sets the function for the relay output M3-
H2-02
M4 function
M4.
selection
Terminal M5-
Sets the function for the relay output M5-
H2-03
M6 function
M6.
selection
Outputs a 200 ms pulse signal when the
watt-hour counter increases by the units
selected.
Watt Hour
0: 0.1 kWh units
H2-06
Output Unit
1: 1 kWh units
Selection
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
Note: Major functions are listed at the end of the table.
Multi-Function Analog Inputs
Terminal A1
0: 0 to 10 V
H3-01
Signal Level
1: –10 to 10 V
Selection
Terminal A1
H3-02
Function
Sets the function of terminal A1.
Selection
Terminal A1
Sets the level of the input value selected in
H3-03
Gain Setting
H3-02 when 10 V is input at terminal A1.
Terminal A1
Sets the level of the input value selected in
H3-04
Bias Setting
H3-02 when 0 V is input at terminal A1.
Terminal A3
0: 0 to 10 V
H3-05
Signal Level
1: –10 to 10 V
Selection
Terminal A3
H3-06
Function
Sets the function of terminal A3.
Selection
Terminal A3
Sets the level of the input value selected in
H3-07
Gain Setting
H3-06 when 10 V is input at terminal A3.
Terminal A3
Sets the level of the input value selected in
H3-08
Bias Setting
H3-06 when 0 V is input at terminal A3.
Description