YASKAWA A1000 Quick Start Manual page 21

Ip23/54 floor standing panel, 400 v class: 90 to 315 kw
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

Type
No.
Pulse train output (Output frequency)
MP
Analog monitor output 1 (Output frequency)
FM
Monitor Output
Analog monitor output 2 (Output current)
AM
Monitor common
AC
DM+ Safety monitor output
Safety monitor output common
DM-
NOTICE: The terminals HC, H1, H2 are used for the Safe Disable function. Do not remove the wire link between HC, H1, or H2 unless
the Safe Disable function is used.
NOTICE: The wiring length to the terminals HC, H1 and H2 should not exceed 30 m.
YASKAWA Europe TOEP C710616 88A - AC Drive A1000 IP23/54 Floor Standing - Quick Start Guide
Terminal Name (Function)
Refer to Safe Disable Input Function on page 40
3 Electrical Installation
Function (Signal Level) Default Setting
32 kHz (max)
-10 to +10 V DC, 0 to +10 V DC, or 4 to 20 mA
Use jumper S5 on the control terminal board to select between
voltage or current output at terminals AM and FM. Set
parameters H4-07 and H4-08 accordingly when changing the
jumper setting.
0 V
Outputs status of Safe Disable function. Closed when both
Safe Disable channels are closed. Up to +48 V DC 50 mA
when using this function.
EN 21