Ethernet; I/O - Extension Boards; Hardware Installation; Software Configuration - Bosch BIS 2.3 Installation Manual

Access engine
Table of Contents

Advertisement

BIS 2.3 - Access Engine
7.2

Ethernet

1.
2.
3.
NOTICE!
To allocate the IP address and the name, use the application
i
AmcIpConfig.exe , which can be started from
<InstallationDisk>\MgtS\Access Engine\AC\Bin and can be
executed from any computer in the network.
7.3

I/O - Extension boards

The AMC2 8I-8O-EXT and AMC2 16I-16O-EXT extension boards
can be connected to the associated only via RS485.
7.3.1

Hardware installation

1.
2.
7.3.2

Software configuration

The hardware installation stipulates that the extension board
be created below the respective AMC.
Bosch Sicherheitssysteme GmbH
Set up the the AMC as described in Section 7.1.1 Creating
the controllers in the device editor.
Select UDP as the interface type.
Enter the IP address of the AMC as the host name.
Connect the 6-pole RS485 extension interface of the AMC
(S1) to the same interface on the extension board.
If the extension board is supplied with voltage via the
AMC, then the supply lines (1 and 2) must be
connected in addition to the data lines.
If the extension board is to be supplied by a separate
power supply , only the data lines from the AMC need
to be connected. The power is supplied via the 7-wire
interface of the extension board.
Open the casing of the extension board and set the
address switch to the desired address. Extension boards
can have addresses 1 to 3.
Installation manual
Connecting the controllers | en
F.01U.028.713 | V 2.3.0.1 | 2009.11
67