11.5
Supervision Functions
Voltage-Balance Supervision
11.5.1
Setting Values
Release threshold
Threshold min/max
Delay failure indication
Dropout Ratio
Overvoltage dropout ratio
Undervoltage dropout ratio
Times
Tripping time
Dropout time
Voltage-Sum Supervision
11.5.2
Setting Values
Threshold
Delay failure indication
Dropout Ratio
Dropout ratio
Times
Tripping time
Dropout time
Voltage Phase-Rotation Supervision
11.5.3
Setting Values
Tripping delay
Phase-rotation direction
Times
Tripping time
Dropout time
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
0.300 V to 170.000 V
0.58 to 0.95
0.00 s to 100.00 s
0.300 V to 170.000 V
0.00 s to 100.00 s
0.00 s to 100.00 s
A B C
A C B
Approx. 500 ms
Approx. 500 ms
Technical Data
11.5 Supervision Functions
Increments of 0.001 V
Increments of 0.01
Increments of 0.01 s
Approx. 0.97
Approx. 1.05
Approx. 500 ms
Approx. 500 ms
Increments of 0.001 V
Increments of 0.01 s
Approx. 0.97
Approx. 500 ms
Approx. 500 ms
Increments of 0.01 s
441