Supervision Functions
8.8 Error Responses and Corrective Measures

Defect severity 1

Defect severity 2
Defect severity 3
Defect severity 4
8.8.2
Defect Severity 1
Defect severity 1 faults allow the continued safe operation of the device. Defect severity 1 faults are indicated.
The device remains in operation.
When the supervision functions pick up, corrupted data and signals are marked as invalid. In this way, the
affected functions can go into a secure state. Whether functions are blocked is decided in the appropriate
function itself. For more detailed information, refer to the function descriptions.
Live status contact
Red error LED
Log
For every device fault, a corresponding supervision indication is generated. The device records these indica-
tions with a real-time stamp in the operational log. In this way they are available for further analyses. If super-
visions in the communication interfaces area of the device pick up, there is a separate communication log
available for each port. Extended diagnostic indications and measured values are available there. The device-
diagnosis log contains expanded fault descriptions. There you also receive recommendations of corresponding
corrective measures for each detected device error.
There is further information on handling the logs in chapter
Group-Warning Indication Group Warning
In the delivery condition, all supervision indications of Defect Severity 1 are routed to the signal
(_:301)Group warning. In this way, a device error can be indicated with only one indication. The majority
of supervision indications are permanently connected to the Group warning (Group warning column =
fixed). However, some supervision indications are routed flexibly to the Group warning via a CFC chart
(Group warning column = CFC). If necessary, you can remove again the routings via a CFC chart from the
group indication.
In delivery condition, the Group warning is prerouted to an LED.
The following logic shows the context.
402
Error Responses
x
x
x
x
x
x
Remains activated
Is not activated
x
During the
x
starting
time of
the device
x
x
x
x
3.1
Indications.
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017