Advertisement

Power-System Data

5.5 Application and Setting Notes for Measuring Point Current 1-Phase (I-1ph)

5.5
Application and Setting Notes for Measuring Point Current 1-Phase
(I-1ph)
If you insert a Measuring point I 1-ph in DIGSI 5, you must route a current to the measuring point under
Name of the device → Measuring-points routing → Current-measuring points.
You can only route the current Ix.
Parameter: Rated primary current
Default setting (_:2311:101) Rated primary current = 1000 A
With the Rated primary current parameter, the active primary rated current of the current transformer
is set.
If you change the setting of the parameter Rated primary current, for example, from 1000 A to 500 A
using the operation panel, restart the device to ensure that the change of the current transformer ratios was
accepted.
Parameter: Rated secondary current
Default setting (_:2311:102) Rated secondary current = 1 A
With the Rated secondary current parameter, you set the current secondary rated current of the current
transformer.
Parameter: Current range
Default setting (_:2311:103) Current range = 100 x IR
The Current range parameter allows you to set the dynamic range for the current input. Please retain the
default setting for power-system protection applications.
Parameter: Tracking
Default setting (_:2311:105) Tracking = active
With the parameter Tracking, you specify whether you would like to work with the sampling-frequency
tracking function.
Parameter Value
active
inactive
Parameter: Term. 1,3,5,7 in dir. of obj.
Default setting (_:2311:116) Term. 1,3,5,7 in dir. of obj. = yes
With the Term. 1,3,5,7 in dir. of obj. parameter, you define the direction of the current. If you set
the parameter Term. 1,3,5,7 in dir. of obj. = yes, the direction of the current to the protected
object is defined as
Parameter: Magnitude correction
Default setting (_:3841:103) Magnitude correction = 1.000
When using the Magnitude correction parameter, you adjust the magnitude (magnitude correction) for
the current input. This allows you to correct the tolerances of the primary current transformer phase-selec-
116
Description
If the parameter Tracking = active has been set, the measuring point
will be included when determining the sampling frequency.
Note: If the parameter Tracking = active, the determined sampling
frequency applies to all functions in the device not using fixed sampling
rates.
If the channels of the measuring point are not to be considered for deter-
mining the sampling frequency, please select the setting value inactive.
forward .
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017