  • Page 1 SIPROTEC 5 V7.90 and higher Hardware Technical Data Extract from manual C53000-G5040-C002-F, chapter 6 Smart Infrastructure...
  • Page 2 Edition: 06.2019 SIPROTEC™, DIGSI™, SIGRA™, SIGUARD™, SAFIR™, SICAM™, Version of the product described: V7.90 and higher and MindSphere™ are trademarks of Siemens AG. Any unauthorized use is prohibited. All other designations in this document may represent trademarks whose use by third parties for their own purposes may violate the propri- etary rights of the owner.
  • Page 3 Preface Purpose of the Manual This manual describes the hardware of the SIPROTEC 5 device family and provides general information on the product structure, the modules and technical data. Target Audience Protection system engineers, commissioning engineers, persons entrusted with the setting, testing and main- tenance of automation, selective protection and control equipment, and operational crew in electrical installa- tions and power plants.
  • Page 4 The help package for DIGSI 5 includes a description of the basic operation of software, the DIGSI princi- ples and editors. The help package for CFC includes an introduction to CFC programming, basic examples of working with CFC, and a reference chapter with all the CFC blocks available for the SIPROTEC 5 range. •...
  • Page 5 Preface Additional Support For questions about the system, please contact your Siemens sales partner. Support Our Customer Support Center provides a 24-hour service. Siemens AG Customer Support Center Humboldtstrasse 59 90459 Nuremberg Germany E-mail: support.energy@siemens.com Training Courses Inquiries regarding individual training courses should be addressed to our Training Center:...
  • Page 6 Used Symbols on Device Symbol Description Direct current, IEC 60417-5031 Alternating current, IEC 60417-5032 Direct and alternating current, IEC 60417-5033 Earth (ground) terminal, IEC 60417-5017 Protective conductor terminal, IEC 60417-5019 SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 7 Description Caution, risk of electric shock Caution, risk of danger, ISO 7000-0434 Protective Insulation, IEC 60417-5172, Safety Class II devices Guideline 2002/96/EC for electrical and electronic devices Guideline for the Eurasian Market SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 8 License Conditions provide for it you can order the source code of the Open Source Software from your Siemens sales contact - against payment of the shipping and handling charges - for a period of at least 3 years since purchase of the Product. We are liable for the Product including the Open Source Software contained in it pursuant to the license conditions applicable to the Product.
  • Page 9 Name Plate of Non-Modular Devices (7xx81, 7xx82) 6.17 Name Plate, UL Approval, Base Module and 1/3 Base Module 6.18 Name Plate, UL Approval, Expansion Module 6.19 Battery 6.20 SDHC Memory Card 6.21 Display Resolution SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 10 20 V continuously NOTE You can find more information on the technical data of the current and voltage transformers in the SIPROTEC 5 Device manuals in the Technical Data chapter. Measuring-Transducer Inputs (via Module ANAI-CA-4EL) Insulation class SELV (Safety Extra Low Voltage) (according to IEC 60255-27)
  • Page 11 DC 20 V continuously DC 60 V continuously (IO210 MT3 terminal point C9) All values in combination with sensors approved by Siemens. Numerical aperture (NA = sin θ (launch angle)) The IO210 has 4 high-speed measuring-transducer inputs. They can be used either as a voltage or current input.
  • Page 12 ELV (Extra Low Voltage) (as per IEC 60255-27) Insulation class IO212 SELV (as per IEC 60255-27) NOTE You can find more information on the measuring accuracy of the analog inputs in the SIPROTEC 5 Device manuals in the Technical Data chapter. Temperature Inputs Settings...
  • Page 13 1/3 base module, modular 13 W 33 VA 24 VA Without plug-in modules 1/6 expansion module 6 VA 6 VA 1/6 plug-in module 3.5 W 14 VA 7 VA assembly without plug-in modules (modules CB202) SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 14 For V ≥ DC 24 V ≥ 20 ms short circuit, non-modular devices For V ≥ DC 60 V ≥ 50 ms IEC 61000-4-11 For V ≥ AC 115 V ≥ 200 ms IEC 61000-4-29 SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 15 Standard Binary Input Rated voltage range DC 24 V to 250 V The binary inputs of SIPROTEC 5 are bipolar, with the exception of the binary inputs on the modules IO230, IO231, and IO233. Current consumption, excited Approx. DC 0.6 mA to 2.5 mA (independent of the control voltage) Power consumption, max.
  • Page 16 For time-critical applications with low-active signals, consider the specified dropout times. If necessary, provide for active discharge of the binary input (for example, a resistor in parallel to the binary input or using a change-over contact). SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 17 DC 48 V, 0.8 A, General Purpose DC 240 V, 0.1 A, General Purpose AC 120 V, 5 A, General Purpose AC 250 V, 5 A, General Purpose AC 250 V, 0.5 hp B300 R300 SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 18 Short-time current across closed contact 250 A for 30 ms Total permissible current for contacts connected to common potential Switching time OOT (Output Operating Time) ≤ 16 ms Additional delay of the output medium used SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 19 4.7 nF, ± 20 %, AC 250 V contacts The power relays operate in interlocked mode, that is, only one relay of each switching pair picks up at a time thereby avoiding a power-supply short circuit. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 20 Base Module Status Color Quantity Green ERROR Routable (adjustable with DIGSI 5) 2-colored: red or green Only the defined color can be used in operation. Expansion Module Status Color Quantity Routable 16 optional SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 21 Return line Pxx-TSIG Return line for P-TSYNC M-TSYNC Screen Shield potential – – P12-TSIG DC 12 V input P-TSYNC DC 24 V input Screen Shield potential Only for the PPS signal (GPS) SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 22 Baud rate 100 Mbit/s Max. line length 20 m with Ethernet patch cable CAT 6 S/FTP, F/FTP, or SF/FTP Insulation class SELV (acc. to IEC 60255-27) Interface design Corresponds to IEEE 802.3, 100Base-TX SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 23 Connection using a special cable. Is part of the device delivery. Insulation class SELV (according to IEC 60255-27) Plug-In Modules You can find the Technical Data for plug-in modules in chapter 4 Plug-In Modules. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 24 150 pF Ri = 330 Ω Radiated electromagnetic field 20 V/m, 80 MHz to 1 GHz immunity 10 V/m, 1 GHz to 6 GHz Frequency sweep 80 % AM IEC 61000-4-3 1 kHz SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 25 If a module ETH-BD-2FO is installed on a PS201 in the top slot (plug-in module position E in Figure 2-8), the immunity for this module is restricted to 3.5 kV at the moment. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 26 Harmonic current emissions (see EN 61000-3-2, section 7, power consumption < 75 W) Loading effect in electricity-supply systems, voltage fluctuations Does not apply! Flicker (see EN 61000-3-3, section 6, no significant voltage fluctuations) SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 27 The non-modular devices in the assembly frame meet class 1. For technical reasons, the frequency range is raised from 1 Hz to 3 Hz at the lower limit. The non-modular devices in the assembly frame meet class 1. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 28 All 24 binary inputs usable 18 binary inputs usable 125 V operating voltage for uninterrupted duty for uninterrupted duty for uninterrupted duty (max. 3 in each group of 4 at the same time) SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 29 Humid heat, cyclical 12 h + 12 h cycles 25 °C/55 °C/95 % relative humidity Other Environmental Information Maximum operating altitude above sea level 2000 m (6561.68 ft) Minimum permissible atmospheric pressure 783.8 hPa SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 30 Removing or plugging in individual modules under live voltage is prohibited. Some components are elec- trostatically sensitive in the removed state. Pay attention to the ESD specifications (Electrostatically Sensi- tive Devices). There is no danger for the components when they are installed. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 31 Transient excess pickup in fundamental component measurement ≤ 5 % method for τ > 100 ms (with complete unbalance) ≤ 1.5 % EMC interference Use shielded cables for the current and voltage measuring inputs on the fault recorder. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 32 Technical Data 6.12 Approvals 6.12 Approvals UL-Listed/UL-Approved Base module and 1/3 base module IND. CONT. EQ. 69CA Expansion module IND. CONT. EQ. 69CA SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 33 337 mm 337 mm on-site operation (5.91 x 12.36 x (8.86 x 12.36 x (11.81 x 12.36 x (14.76 x 12.36 x (17.72 x 12.36 x panel 13.27) 13.27) 13.27) 13.27) 13.27) SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 34 IP2x for voltage terminal (installed) Degree of pollution, IEC 60255-27 Maximum operating altitude above sea level 2000 m (6561.68 ft) The provided plug-in label must be used for expansion modules with LEDs. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 35 1.2 Nm M4 x 8 1.2 Nm M2.5 x 6 0.39 Nm Countersunk screw, M2.5 x 6 0.39 Nm Countersunk screw, M2.5 x 8 0.39 Nm Collar screw, M4 x 20 0.7 Nm SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 36 Technical Data 6.14 Assembly Dimensions 6.14 Assembly Dimensions Flush-Mounting Device [dw_z1_1-3, 2, en_US] Figure 6-1 Cut-Out Widths and Drilling Pattern – 1/3 Device, 1st Device Row SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 37 Technical Data 6.14 Assembly Dimensions [dw_z1_1-2, 2, en_US] Figure 6-2 Cut-Out Widths and Drilling Pattern – 1/2 Device, 1st Device Row SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 38 Technical Data 6.14 Assembly Dimensions [dw_z1_2-3, 2, en_US] Figure 6-3 Cut-Out Widths and Drilling Pattern – 2/3 Device, 1st Device Row SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 39 [dw_z1_5-6, 2, en_US] Figure 6-4 Cut-Out Widths and Drilling Pattern – 5/6 Device, 1st Device Row [dw_z1_1-1, 3, en_US] Figure 6-5 Cut-Out Widths and Drilling Pattern – 1/1 Device, 1st Device Row SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 40 All drillings in the area of the specific device cut-out widths (see Table 6-7) must comply with the dimensions in the corresponding figures. [dw_z2_2-6, 2, en_US] Figure 6-6 Cut-Out Widths and Drilling Pattern – 1/3 Device, 2nd Device Row SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 41 [dw_z2_3-6, 2, en_US] Figure 6-7 Cut-Out Widths and Drilling Pattern – 1/2 Device, 2nd Device Row [dw_z2_4-6, 2, en_US] Figure 6-8 Cut-Out Widths and Drilling Pattern – 2/3 Device, 2nd Device Row SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 42 [dw_z2_5-6, 2, en_US] Figure 6-9 Cut-Out Widths and Drilling Pattern – 5/6 Device, 2nd Device Row [dw_z2_6-6, 3, en_US] Figure 6-10 Cut-Out Widths and Drilling Pattern – 1/1 Device, 2nd Device Row SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 43 Drilling Pattern – 1/1 Devices, 1st and 2nd Device Row Siemens recommends a drilling space of at least 55 mm (2.17 in) between the 1st and 2nd device row. Due to the connecting-cable length, the maximum space may be approx. 80 mm (3.15 in). The length of the cable is 890 mm (35.04 in) from the center of the plug to the center of the plug.
  • Page 44 145 (5.71) 1/2 device 220 (8.66) 2/3 device 295 (11.61) 5/6 device 370 (14.57) 1/1 device 445 (17.52) [dw_surface_mounting_in, 2, en_US] Figure 6-13 Flush-Mounting Devices, Dimensions from the Side and Front Views SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 45 1/3 Surface-Mounted Device with Integrated On-Site Operation Panel, Dimensions in the Side and Front Views NOTE For surface-mounted devices, make sure that the drillings fit for a screw of the size M6. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 46 [dwbohrge-1_3.vsd, 2, en_US] Figure 6-15 Drilling Pattern of a 1/3 Surface-Mounted Device – 1st Device Row [dwbohrge-1_2.vsd, 2, en_US] Figure 6-16 Drilling Pattern of a 1/2 Surface-Mounted Device – 1st Device Row SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 47 [dwbohrge-2_3.vsd, 2, en_US] Figure 6-17 Drilling Pattern of a 2/3 Surface-Mounted Device – 1st Device Row [dwbohrge-5_6.vsd, 2, en_US] Figure 6-18 Drilling Pattern of a 5/6 Surface-Mounted Device – 1st Device Row SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 48 [dwbohrge-070211-01.tif, 3, en_US] Figure 6-19 Drilling Pattern of a 1/1 Surface-Mounted Device – 1st Device Row [dw_z2_bohr_1-3.vsd, 2, en_US] Figure 6-20 Drilling Pattern of a 1/3 Surface-Mounted Device – 2nd Device Row SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 49 [dw_z2_bohr_1-2.vsd, 2, en_US] Figure 6-21 Drilling Pattern of a 1/2 Surface-Mounted Device – 2nd Device Row [dw_z2_bohr_2-3.vsd, 2, en_US] Figure 6-22 Drilling Pattern of a 2/3 Surface-Mounted Device – 2nd Device Row SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 50 Technical Data 6.14 Assembly Dimensions [dw_z2_bohr_5-6.vsd, 2, en_US] Figure 6-23 Drilling Pattern of a 5/6 Surface-Mounted Device – 2nd Device Row SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 51 Technical Data 6.14 Assembly Dimensions [dw_z2_bohr_1-1.vsd, 2, en_US] Figure 6-24 Drilling Pattern of a 1/1 Surface-Mounted Device – 2nd Device Row SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 52 Side and Front Views Surface-Mounted Devices with Integrated On-Site Operation Panel (Non-Modular Device) NOTE For surface-mounted devices, make sure that the drillings fit for a screw of the size M6. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 53 You can find more information on the drilling patterns for the devices in section Surface-Mounted Devices with Integrated On-Site Operation Panel (Modular Device) , Page 241. [dw_z1_osop_1-3, 1, en_US] Figure 6-27 Drilling Pattern of the On-Site Operation Panel of the 1/3 Device SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 54 [dw_z1_osop_1-2, 1, en_US] Figure 6-28 Drilling Pattern of the On-Site Operation Panel of the 1/2 Device [dw_z1_osop_2-3, 1, en_US] Figure 6-29 Drilling Pattern of the On-Site Operation Panel of the 2/3 Device SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 55 [dw_z1_osop_5-6, 1, en_US] Figure 6-30 Drilling Pattern of the On-Site Operation Panel of the 5/6 Device [dw_z1_osop_1-1, 1, en_US] Figure 6-31 Drilling Pattern of the On-Site Operation Panel of the 1/1 Device SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 56 Table 6-8 for the variable dimension a. The drilling patterns correspond to the figures Figure 6-15 Figure 6-24. The cable length for the detached operation panel is up to 5 m (196.85 in). SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 57 5 kV impulse voltage test [type test] in compliance with Class III European CE marking Pay attention to the overall documentation for the device (Product information, Device manual, Hardware manual, Operating manual, and Communication protocol manuals) SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 58 5 kV impulse voltage test [type test] in compliance with Class III European CE marking Pay attention to the overall documentation for the device (Product information, Device manual, Hardware manual, Operating manual, and Communication protocol manuals) SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 59 The ambient temperature must not exceed 70 °C or 158 °F Surr during normal operation. : max. 100 VA Maximum power consumption of the device For additional output ratings see product infor- For additional output ratings see Product information. mation SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 60 The ambient temperature must not exceed 70 °C or 158 °F Surr during normal operation. Listed accessory for use with manufacturer´s Approved accessory for use with a protection device from protection relay. Siemens SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 61 10 years removed Use button cells from manufacturers like Varta, Panasonic, or Duracell. NOTE After the Battery fault indication, you must replace the battery within 2 weeks. If ignored, data loss may occur. SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...
  • Page 62 Technical Data 6.20 SDHC Memory Card 6.20 SDHC Memory Card NOTE You can use only Siemens SDHC memory cards. Capacity 16 GB Performance class ≥ Class 10 Temperature range -40 °C to +85 °C Flash type Dimensions Width x Height x Depth (in Inches) SDHC memory card 24 mm x 32 mm x 2.1 mm (0.94 x 1.26 x 0.08)
  • Page 63 Technical Data 6.21 Display Resolution 6.21 Display Resolution LCD Graphic display (Liquid Crystal Display) Small 192 x 128 pixels LCD Graphic display (Liquid Crystal Display) Large 240 x 320 pixels SIPROTEC 5, Hardware Description, Manual C53000-G5040-C002-F, Edition 06.2019...