Communication With An Rtd Unit - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

6.5.7.3

Communication with an RTD Unit

Logic
[lortdtcp-311012-01.tif, 1, en_US]
Figure 6-57
Communication with an RTD Unit
The function is used to communicate with an RTD box connected via an Ethernet connection. If the connec-
tion of the function is successfully established to the external RTD box via the Ethernet interface, the RTD box
transmits the temperatures of all connected sensors to the RTD box Ether. function. For the connection to be
established successfully, specific communication settings must be set, see chapter
Setting
Notes.
The RTD box Ziehl TR1200 IP supports only an Ethernet connection of 10 MBit/s. A direct connection to a 100-
Mbit communication module is therefore not possible. For this reason, you must connect the RTD box to the
communication module via a 10/100 MBit/s autosensing switch which automatically recognizes the transmis-
sion rates and adapts them accordingly. Further information can be found in the Application and setting
notes, see chapter
Error Responses
The following table lists the conditions under which the
state.
Table 6-9
Error Description
The RTD unit Ether. function cannot establish a
connection with a communication module.
The connection between the communication module
and the RTD unit causes a time-out.
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Logic of the RTD Unit Ether. Function
6.5.7.4 Application and Setting
Error Responses
6.5 Function-Group Type Analog Units
Notes.
Health status transitions to the Alarm or Warning
Status Health
Alarm
Warning
Function-Group Types
6.5.7.4 Application and
197