Function-Group Types
6.5 Function-Group Type Analog Units
Parameter: Temperature unit
To change the display and evaluation of measured temperature values from °C to °F, adapt the DIGSI user
default settings accordingly.
Proceed as follows:
•
In DIGSI select the menu item Extras --> Settings.
•
In the Settings view select the menu item DIGSI 5 User preferences.
•
Under Standard unit system change the setting value of the unit system used from
units .
[scfahrht-190214-01, 1, en_US]
Figure 6-59
The following settings and information table shows only 1 of the 12 sensors, as the setting possibilities of the
12 sensors do not differ.
6.5.7.7
Settings
Addr.
General
_:2311:103
_:2311:106
Sensor 1
_:11611:102
Sensor 2
_:11612:102
200
Change of the Display Between °C and °F
Parameter
General:Port
General:Slave address
Sensor 1:Sensor type
Sensor 2:Sensor type
C
Setting Options
•
port F
•
port E
•
port P
•
port N
•
port J
1 to 254
•
Pt 100
•
Ni 100
•
Ni 120
•
Pt 100
•
Ni 100
•
Ni 120
SI units to US
Default Setting
port J
1
Pt 100
Pt 100
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017