Information List - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Fault Recorder
7.4 Trigger Functions 1-Phase
Addr.
_:9751:105
_:9751:113
_:9751:102
_:9751:106
_:9751:114
_:9751:103
_:9751:107
_:9751:115
_:9751:104
_:9751:108
_:9751:116
_:9751:112
7.4.2.7

Information List

No.
Trig. I RMS 1
_:9781:54
_:9781:52
_:9781:53
_:9781:301
284
Parameter
C
Trig. I fund 1:Max.
1 A @ 100 Irated 0.030 A to 100.000 A
trigger
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I fund 1:Max.
trigger hysteresis
Trig. I fund 1:Min.
trigger active
Trig. I fund 1:Min.
1 A @ 100 Irated 0.030 A to 100.000 A
trigger
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I fund 1:Min.
trigger hysteresis
Trig. I fund 1:dM/dt rise
active
Trig. I fund 1:dM/dt rise
1 A @ 100 Irated 0.030 A to 100.000 A
(/Filter time)
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I fund 1:dM/dt rise
hysteresis
Trig. I fund 1:dM/dt drop
active
Trig. I fund 1:dM/dt drop
1 A @ 100 Irated 0.030 A to 100.000 A
(/Filter time)
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I fund 1:dM/dt drop
hysteresis
Trig. I fund 1:Filter time
Information
Trig. I RMS 1:Inactive
Trig. I RMS 1:Behavior
Trig. I RMS 1:Health
Trig. I RMS 1:Trigger active
Setting Options
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.900 p.u. to 0.990 p.u.
no
yes
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
1.010 p.u. to 1.100 p.u.
no
yes
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.900 p.u. to 0.990 p.u.
no
yes
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.900 p.u. to 0.990 p.u.
2 cycles to 250 cycles
Data Class
(Type)
SPS
ENS
ENS
SPS
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Default Setting
1.200 A
6.00 A
1.200 A
6.00 A
1.200 A
6.000 A
0.980 p.u.
yes
0.800 A
4.00 A
0.800 A
4.00 A
0.800 A
4.000 A
1.020 p.u.
no
0.300 A
1.50 A
0.300 A
1.50 A
0.300 A
1.500 A
0.980 p.u.
no
0.300 A
1.50 A
0.300 A
1.50 A
0.300 A
1.500 A
0.980 p.u.
2 cycles
Type
O
O
O
O

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siemens 7ke85

Table of Contents