Power-System Data
5.8 Settings
5.8
Settings
General Information
Addr.
General
_:2311:101
Measuring Point I-3ph
Addr.
General
_:8881:115
_:8881:127
_:8881:130
CT phases
_:8881:101
_:8881:102
_:8881:117
_:8881:118
_:8881:116
_:8881:114
_:8881:107
_:8881:108
_:8881:109
CT IN
_:8881:104
_:8881:105
_:8881:119
_:8881:120
124
Parameter
C
General:Phase sequence
Parameter
C
CT 3-phase:CT connec-
tion
CT 3-phase:Tracking
CT 3-phase:Measuring-
point ID
CT 3-phase:Rated
primary current
CT 3-phase:Rated secon-
dary current
CT 3-phase:Current
range
CT 3-phase:Internal CT
type
CT 3-phase:Neutr.point
in dir.of ref.obj
CT 3-phase:Inverted
phases
CT 3-phase:CT error
changeover
CT 3-phase:CT error A
CT 3-phase:CT error B
CT 3-phase:Rated
primary current
CT 3-phase:Rated secon-
dary current
CT 3-phase:Current
range
CT 3-phase:Internal CT
type
Setting Options
•
ABC
•
ACB
Setting Options
•
not assigned
•
3-phase + IN
•
3-phase
•
3-phase + IN-separate
•
3-phase, 2 primary CT
•
2ph, 2p. CT + IN-sep
•
inactive
•
active
0 to 100
1.0 A to 100000.0 A
•
1 A
•
5 A
•
1.6 x IR
•
100 x IR
•
CT protection
•
CT measurement
•
CT Process bus
•
no
•
yes
•
none
•
AC
•
BC
•
AB
1.00 to 10.00
0.5 % to 50.0 %
0.5 % to 50.0 %
1.0 A to 100000.0 A
•
1 A
•
5 A
•
1.6 x IR
•
100 x IR
•
CT protection
•
CT measurement
•
CT Process bus
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Default Setting
ABC
Default Setting
3-phase + IN
active
0
1000.0 A
1 A
100 x IR
CT protection
yes
none
1.00
5.0 %
15.0 %
1000.0 A
1 A
100 x IR
CT protection