Powerware 9330 Installation And Operation Manual page 177

10 kva -- 20 kva 25 kva -- 40 kva
Table of Contents

Advertisement

Basic unit ratings at
0.7 lagging PF load
gg g
AC Input to UPS Rectifier
AC Input to UPS Rectifier
3 , 1 gnd
3 , 1 gnd
AC
AC
INPUT
Minimum conductor size (number per  )
*(Maximum amps includes full load current plus
battery recharge current)
AC Input to Module Bypass (UPS Bypass)
Full Load Current
Full Load Current
AC
AC
INPUT
Minimum conductor size (number per  )
DC Input from External Battery Source to UPS
DC
( ) pos t e, ( ) egat e, ( ) g d
(1) positive, (1) negative, (1) gnd
INPUT
INPUT
Minimum conductor size (number per pole)
AC Output to Critical Load
AC
AC
Full Load Current 3 , (1) Neutral, (1) gnd
Full Load Current 3  (1) Neutral (1) gnd
OUTPUT
Minimum conductor size (number per  )
Basic unit ratings at
0.7 lagging PF load
gg g
AC Input to UPS Rectifier
AC Input to UPS Rectifier
3 , 1 gnd
3 , 1 gnd
AC
AC
INPUT
Minimum conductor size (number per  )
*(Maximum amps includes full load current plus
battery recharge current)
AC Input to Module Bypass (UPS Bypass)
Full Load Current
Full Load Current
AC
AC
INPUT
Minimum conductor size (number per  )
DC Input from External Battery Source to UPS
DC
(1) positive, (1) negative, (1) gnd
( ) pos t e, ( ) egat e, ( ) g d
INPUT
INPUT
Minimum conductor size (number per pole)
AC Output to Critical Load
AC
AC
Full Load Current 3 , (1) Neutral, (1) gnd
Full Load Current 3  (1) Neutral (1) gnd
OUTPUT
Minimum conductor size (number per  )
NOTE:
Callout letter
map to drawing #164201300---6
Powerware 9330 (10 kVA- -40 kVA) Installation and Operation
164201300 REV. G 061502
Table I. INPUT/OUTPUT Ratings & External Wiring Requirements for
Powerware 9330---40/35
(Without Options Cabinet)
Ratings
(0.95min.PF)
(0.95min.PF)
3 , (1) Neutral, (1) gnd
3 , (1) Neutral, (1) gnd
Table J. INPUT/OUTPUT Ratings & External Wiring Requirements for
Powerware 9330---40/40
(Without Options Cabinet)
Ratings
(0.95min.PF)
(0.95min.PF)
3 , (1) Neutral, (1) gnd
3 , (1) Neutral, (1) gnd
and
,
,
,
Units
KVA
KW
INPUT/OUTPUT
VOLTAGE
A
AWG or kcmil(ea)
Amps
B
AWG or kcmil(ea)
VDC (Nominal)
C
Amps
(See note 8)
AWG or kcmil(ea)
Amps
D
AWG or kcmil(ea)
Units
KVA
KW
INPUT/OUTPUT
VOLTAGE
A
AWG or kcmil(ea)
Amps
B
AWG or kcmil(ea)
VDC (Nominal)
C
Amps
(See note 8)
AWG or kcmil(ea)
Amps
D
AWG or kcmil(ea)
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201300---1
REVISION: G
Rating 50/60 Hz
35
24.5
208
Amps*
Amps*
92
92
2 (1)
97
1 (1)
288
91
2 (1)
97
1 (1)
Rating 50/60 Hz
40
28
208
Amps*
Amps*
100
100
1 (1)
111
2/0 (1)
288
100
1 (1)
111
2/0 (1)
SHEET:
DATE:
061502
6 of 17
A ---7