Terminals are UL and CSA rated at 90˚C. Refer to Tables N through Q for power cable
terminations, and Table R and U for conduit requirements. Drawings 164201300---8
through 164201300---12 show the location of the power cable terminals inside the UPS,
Options, and Battery Cabinets.
Table N. UPS Cabinet Power Cable Terminations Powerware 9330 (10 kVA---20 kVA)
Terminal Function
AC Input to UPS
p
Rectifier and Bypass
(TB2)
(TB2)
(Single Input)
(Single Input)
AC Input to UPS
p
Rectifier (CB1)
C
(Dual Input)
(Dual Input)
AC Input To Bypass
p
(TB2)
(Dual Input)
(Dual Input)
AC Output to Critical
p
Load
(Part of TB3)
(Part of TB3)
DC Input from
Battery to UPS
atte y to U S
External Battery
Input to UPS
S
(Part of TB3)
(Part of TB3)
Customer Ground
NOTE: Customer ground, size 1/0, can be
run in any conduit listed in Table R.
A ---10
Terminal
Function
A
A
Phase A
Phase A
B
B
Phase B
Phase B
C
C
Phase C
Phase C
N
N
Neutral
Neutral
A
Phase A
B
Phase B
C
Phase C
yp
A
A
Phase A
Phase A
B
B
Phase B
Phase B
C
C
Phase C
Phase C
N
N
Neutral
Neutral
A
A
Phase A
Phase A
B
B
Phase B
Phase B
C
C
Phase C
Phase C
N
N
Neutral
Neutral
N/A
Battery
(+)
N/A
Battery
(---)
y
Battery
y
Positive
Positive
+
Battery
y
Negative
Negative
---
Ground
Ground
Size of Pressure
Termination
Vendor
Entrelec
1 --- #14---#4
1
#14 #4
Phoenix
Entrelec
1 --- #14---#4
1
#14 #4
Phoenix
Entrelec
1 --- #14---#4
1
#14 #4
Phoenix
Entrelec
1
1 --- #4---#0
#4 #0
Phoenix
1 --- #18---#2
N/A
1 --- #18---#2
N/A
1 --- #18---#2
N/A
Entrelec
1 --- #14---#4
1
#14 #4
Phoenix
Entrelec
1
1 --- #14---#4
#14 #4
Phoenix
Entrelec
1 --- #14---#4
1
#14 #4
Phoenix
Entrelec
1
1 --- #4---#0
#4 #0
Phoenix
Entrelec
1
1 --- #14---#4
#14 #4
Phoenix
Entrelec
1
1 --- #14---#4
#14 #4
Phoenix
Entrelec
1 --- #14---#4
1
#14 #4
Phoenix
Entrelec
1
1 --- #4---#0
#4 #0
Phoenix
Red Battery
N/A
Connector
Black Battery
N/A
Connector
Entrelec
1 --- #14---#0
1
#14 #0
Phoenix
Entrelec
1 --- #14---#0
1
#14 #0
Phoenix
2 --- #14---#1/0
N/A
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201300---1
REVISION:
F
Powerware 9330 (10 kVA- -40 kVA) Installation and Operation
Tightening Torque
Type
N-M (lb-in.)
Screw
1.3-1.4 (11-12)
Slotted
Slotted
1.5-1.8 (13-16)
1.3-1.4 (11-12)
Slotted
Slotted
1.5-1.8 (13-16)
1.3-1.4 (11-12)
Slotted
Slotted
1.5-1.8 (13-16)
2.5-2.9(22-26)
Slotted
Slotted
3.2-3.7(28-33)
2.0 (17.5)
Phillips
2.0 (17.5)
Phillips
2.0 (17.5)
Phillips
1.3-1.4 (11-12)
Slotted
Slotted
1.5-1.8 (13-16)
1.3-1.4 (11-12)
Slotted
Slotted
1.5-1.8 (13-16)
1.3-1.4 (11-12)
Slotted
Slotted
1.5-1.8 (13-16)
2.5-2.9(22-26)
Slotted
Slotted
3.2-3.7(28-33)
1.3-1.4 (11-12)
Slotted
Slotted
1.5-1.8 (13-16)
1.3-1.4 (11-12)
Slotted
Slotted
1.5-1.8 (13-16)
1.3-1.4 (11-12)
Slotted
Slotted
1.5-1.8 (13-16)
2.5-2.9(22-26)
Slotted
Slotted
3.2-3.7(28-33)
N/A
N/A
N/A
N/A
)
2.5-2.9(22-26
Slotted
Slotted
3.2-3.7(28-33)
2.5-2.9(22-26)
Slotted
Slotted
3.2-3.7(28-33)
5.6 (50)
Slotted
SHEET:
DATE:
111501
164201300 REV. G 061502
9 of 17