Powerware 9330 Installation And Operation Manual page 184

10 kva -- 20 kva 25 kva -- 40 kva
Table of Contents

Advertisement

Table S. Power Cable Conduit Requirements Powerware 9330 (20 kVA)
Powerware
System
9330-20/20
9330-20/20
9330-20/20
9330---20/20
A ---14
Voltage
Terminal
AC Input to UPS
(A, B, C, Gnd)
208
AC Input to Bypass
(A, B, C, Neut, Gnd)
AC
AC
Output
(A, B, C, Neut, Gnd)
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
480
AC
C
(A, B, C, Neut, Gnd)
Output
(A, B, C, Neut, Gnd)
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
600
(A, B, C, Neut, Gnd)
AC
C
Output
(A, B, C, Neut, Gnd)
288
External Battery DC Source
DC
(Positive, Negative, Gnd)
Number of
Wires in
Conduit
4
5
5
4
5
5
4
5
5
3
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201300---1
REVISION:
F
Powerware 9330 (10 kVA- -40 kVA) Installation and Operation
Minimum
Conduit
Number of
Trade Size
Conduits
(inches)
1
1
1
1
1
1
1/2
1
3/4
1
3/4
1
1/2
1
1/2
1
1/2
1
3/4
1
SHEET:
13 of 17
DATE:
111501
164201300 REV. G 061502