Powerware 9330 Installation And Operation Manual page 188

10 kva -- 20 kva 25 kva -- 40 kva
Table of Contents

Advertisement

16.
Output overcurrent protection and output disconnect switch are to be provided by the
user. Table W lists the maximum rating for output circuit breakers satisfying the criteria for
both.
17.
Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC.
Rated battery current is computed at the computed voltage.
A ---18
Table W. Maximum Output Circuit Breaker Ratings
Powerware System
Powerware System
9330---20/10
9330---20/15
9330---20/20
9330---40/25
9330---40/30
9330---40/35
9330---40/40
Output Voltage Rating
208V
480V
35
15
60
25
70
30
90
40
110
45
125
60
150
60
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201300---1
REVISION:
D
Powerware 9330 (10 kVA- -40 kVA) Installation and Operation
600V
15
20
25
30
40
45
50
SHEET:
17 of 17
DATE:
053001
164201300 REV. G 061502