No.
Name
(Hex.)
C3-22
Motor 2 Slip Comp
DelayTime
(0241)
RUN
C3-23
Motor 2 Slip
Compensation
(0242)
Limit
RUN
C3-24
Motor 2 Slip Comp
@ Regen Select
(0243)
RUN
C3-28
Adaptive Slip
Contrl Mode Select Selects the mode for the slip compensation function.
(1B5B)

C4: Torque Compensation

No.
Name
(Hex.)
C4-01
Torque
Compensation
(0215)
Gain
RUN
C4-02
Torque
Compensation
(0216)
Delay Time
RUN
C4-03
Torque
Compensation @
(0217)
FWD Start
C4-04
Torque
Compensation @
(0218)
REV Start
C4-05
Torque
Compensation
(0219)
Time
C4-06
Motor 2 Torque
Comp Delay Time Sets the value if ov [Overvoltage] occurs with sudden changes in the
(021A)
C4-07
Motor 2 Torque
Compensation
(0341)
Gain
RUN
C4-19
T-ripple suppress
freq
(0B8D)
C4-20
vol compensation
adjust 1
(0BCB)
C4-21
vol compensation
adjust 2
(0BCC)
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Adjusts the slip compensation delay time for motor 2 when speed is
unstable or when the slip compensation response is too slow.
Normally there is no need to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the upper limit for the slip compensation function as a
percentage of the motor 2 rated slip.
V/f
CL-V/f
OLV
CLV
AOLV
Enables or disables slip compensation for motor 2 during
regenerative operation.
0 : Disabled
1 : Enabled (6 Hz and above)
2 : Enabled (compensation provided wherever possible)
V/f
CL-V/f
OLV
CLV
AOLV
0 : Normal
1 : Advance
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain for the torque compensation function. Sets the gain for
motor 1 when multiple motors are driven.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the torque compensation delay time in milliseconds. Normally
there is no need to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the amount of torque reference at start in the forward direction
as a percentage of the motor rated torque.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the amount of torque reference at start in the reverse direction
as a percentage of the motor rated torque.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the starting torque constant used with C4-03 and C4-04
[Torque Compensation @ REV Start].
V/f
CL-V/f
OLV
CLV
AOLV
load, at the end of acceleration, or at the start of deceleration.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor 2 gain for the torque compensation function when
using the Motor Switch function.
V/f
CL-V/f
OLV
CLV
AOLV
Increase the setting in increments of approximately 1.0 when current
ripples and torque ripples occur during low-speed operation. If this
still does not improve the situation, set C4-19 = 0 to disable this
function. Normally there is no need to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
This parameter compensates the voltage accuracy. Normally there is
no need to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
This parameter compensates the voltage accuracy. Normally there is
no need to change this setting.
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
10.6 C: Tuning
Default
Ref.
(Range)
Determined by E3-
651
01
(0 - 10000 ms)
200%
651
(0 - 250%)
0
651
(0 - 2)
0
652
(0, 1)
Default
Ref.
(Range)
Determined by A1-
652
02
(0.00 - 2.50)
Determined by A1-
653
02
(0 - 60000 ms)
0.0%
653
(0.0 - 200.0%)
0.0%
653
(-200.0 - 0.0%)
10 ms
653
(0 - 200 ms)
150 ms
653
(0 - 10000 ms)
1.00
654
(0.00 - 2.50)
0.1 Hz
654
(0.0 - 10.0 Hz)
120
654
(0 - 200)
5
654
(0 - 10)
413
10