LIST OF NECESSARY MATERIALS/TOOLS

Additional hardware and miscellaneous supplies are needed for installation. These items are field supplied and must
be sourced before installation. This list also includes tools needed for installation.
List of Materials/Tools
Personal protective equipment/safety devices/ anti-
static wrist straps
SGR-5W Supply Grille and RGR-5W Return Grille
Field-fabricated sleeves (if necessary)
Bottom mounting bracket #113-140 (optional)
Fasteners sufficient for mounting the units such as
5/16" diameter anchor/lag bolts
7/8" diameter washers
Fasteners appropriate for the shelter wall
construction to attach the controller to the wall
Commercial grade outdoor silicone sealant
Miscellaneous hand and power tools and jobsite or
shop materials
Lifting equipment with the necessary capacity and
rigging to safely move/install the systems
Water to prime drain traps
Electrical supplies
-
Various size circuit breakers for the shelter AC
breaker box (see Table 3 on page 16)
-
High-voltage wire of various gauges
(see Table 3)
-
16 gauge minimum, 14 gauge maximum
power wire to connect controller to shelter
power source
-
5-wire, 18 gauge shielded cable with drain
for remote temperature and humidity sensors
(2-wire, 18 gauge shielded cable with drain for
temperature-only sensors)
-
Communication wire: 2-wire, 18 gauge,
shielded with drain
-
18 gauge non-shielded wire for connecting
smoke detector, hydrogen detector and/or
generator, if applicable, to controller
-
CAT 6 Ethernet cable of field-determined length
(for remote communication, if applicable)
-
Miscellaneous electrical supplies including
rigid/flexible conduit and fittings, 2" x 4"
junction boxes (one per temperature/humidity
sensor), wire connectors and supports
Manual 2100-674A
Page
6 of 41
The following is required and must be sourced prior
to installation of these units.
• One (1) 5A circuit breaker for the shelter DC
power plant (for the controller)
Circuit breakers for Emerson Network Power (ENP)
power plants (used in most telecomm shelters built
today) are available directly through the following
distributors:
• Emerson Network Power: 440.288.1122
• Master Electronics: 888.473.5297 or
www.onlinecomponents.com
Emerson Network Power (ENP) Part Number
• 5A circuit breaker: P/N 101598
Always confirm the application before ordering.