4) Press UP or DOWN keys to scroll to Indoor
Temperature 1 (C6).
5) Press ENTER key to scroll to Enable (see
Figure 42).
6) Press UP or DOWN key to change value to ON
to enable sensor (or change value to OFF to
disable sensor).
FIGURE 42
Configuring Indoor Temperature 1 Sensor
To enable/disable Indoor Temperature 2:
1) Press MENU key to go to the Main Menu
screen.
2) Press UP or DOWN keys and ENTER key to
enter TECHNICIAN password 1313.
3) Press UP or DOWN keys to scroll to IO Config;
press ENTER key.
4) Press UP or DOWN keys to scroll to Indoor
Temperature 2 (C7).
5) Press ENTER key to scroll to Enable (see
Figure 43).
6) Press UP or DOWN key to change value to ON
to enable sensor (or change value to OFF to
disable sensor).
FIGURE 43
Configuring Indoor Temperature 2 Sensor
Manual 2100-674A
Page
38 of 41
To enable/disable Indoor Temperature 3:
1) Press MENU key to go to the Main Menu
screen.
2) Press UP or DOWN keys and ENTER key to
enter TECHNICIAN password 1313.
3) Press UP or DOWN keys to scroll to IO Config;
press ENTER key.
4) Press UP or DOWN keys to scroll to Indoor
Temperature 3 (C8).
5) Press ENTER key to scroll to Enable (see
Figure 44).
6) Press UP or DOWN key to change value to ON
to enable sensor (or change value to OFF to
disable sensor).
FIGURE 44
Configuring Indoor Temperature 3 Sensor
See LV1000 Service Instructions manual 2100-
673 for information on setting up the smoke,
hydrogen, generator and power loss relays.

6. Enter Total Number of Units

1) Press MENU key to go to the Main Menu
screen.
2) Press UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to Sys Config;
press ENTER key.
4) Press UP or DOWN keys to scroll to Unit Setup
(A1); press ENTER key.
5) Press ENTER key to scroll to Total Units (see
Figure 45).
6) Press UP or DOWN keys to adjust value to
correct number of units.
7) Press ENTER key to save value.
NOTE: The cooling and heating setpoints are
also displayed on the Unit Setup (A1)
screen. See CONTROL OPERATION in
LV1000 Service Instructions 2100-673 for
information on adjusting the cooling and
heating setpoints. Information on changing
UOM (Units of Measure) and Continuous