Up to two additional temperature and humidity sensors can be purchased and installed. Alternately, temperature-
only sensors can be purchased and installed instead of the combination sensors. Use shielded cable to connect
additional sensors to controller.
Up to two additional temperature/humidity sensors may be added. Be sure the sensors are connected to the proper
terminals on the terminal block and sensor as listed below. See page 22 for information on correct sensor jumper
position.
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
Optional Remote
Temperature/Humidity Sensor
Terminals 26, 27, 20, 21 & 31
Optional Remote
Temperature/Humidity Sensor
Terminals 28, 29, 22, 23 & 32
Temperature-only sensors can be used in place of the additional temperature/humidity sensors. #2 temperature-only sensor
will connect to TB# 26 and 27. #3 temperature-only sensor will connect to TB# 28 and 29. The wire connections for the
temperature-only sensors are not polarity sensitive.
Additional Remote Temperature and Temperature/Humidity Sensor Installation
2
3
2
3
TB#
26
27
2
20
21
31
TB#
28
29
3
22
23
32
FIGURE 20
LV1000 Terminal Block
2
3
2
2
3
3
Sensor
NTC OUT Indoor Temperature 2
NTC OUT Ground
OUT H
Indoor Humidity 2 Signal: 0-1 VDC
M (G)
Indoor Humidity 2 Common
+ (G)
Indoor Humidity 2 Power
Sensor
NTC OUT Indoor Temperature 3
NTC OUT Ground
OUT H
Indoor Humidity 3 Signal: 0-1 VDC
M (G)
Indoor Humidity 3 Common
+ (G)
Indoor Humidity 3 Power
Description
Description
Manual 2100-674A
Page
Wire
Mark
B7
GND
B3
GND
+VDC
Wire
Mark
B8
GND
B4
GND
+VDC
23 of 41