Running in Stand Alone (Orphan) Mode

With the AC breakers turned on, each FUSION-TEC
wall-mount unit has the capability to run without the
LV1000 controller attached—this feature is called
stand alone or orphan mode. This keeps the shelter
between 60°F and 79°F (factory default settings) by
the use of the factory-installed return air sensor in
each wall-mount unit. In stand-alone mode, the wall
unit uses a continuous blower setting to circulate room
air into the return air inlet and uses the return air
temperature sensor to control room temperature.
The wall-mount unit can be turned on and off with
the TEC-EYE hand-held diagnostic tool. When ON is
chosen, the wall unit will heat or cool. The blower will
continue to run when OFF is chosen. If the wall unit is
turned OFF by the TEC-EYE while in stand alone mode
and power is interrupted, when repowered the blower
will not run until the wall unit is turned back ON by the
TEC-EYE.
To turn the unit on or off with TEC-EYE:
1. Connect the TEC-EYE diagnostic tool to the control
board located in the unit.
2. Press MENU key to go to the Main Menu screen.
3. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
4. Press UP or DOWN keys to scroll to On/Off; press
ENTER key.
5. Press UP or DOWN keys to change value from On
to Off or from Off to On.
6. Press ESCAPE key several times to return to Main
Menu screen.
To verify or change the wall-mount unit cooling and
heating setpoints in stand alone mode:
1. Connect the TEC-EYE diagnostic tool to the control
board located in the unit.
2. From the Status screen, press UP or DOWN key
until Quick Menu displays Setpoints (SET) icon.
Press ENTER key.
3. Press ENTER key to scroll to the selected choice
(see Figure 16).
4. Press UP or DOWN key on desired value until value
displays correctly.
5. Press ENTER key to save and scroll to next
parameter.
6. Press ESCAPE key until Main Menu screen is
displayed.

PRELIMINARY START UP

FIGURE 16
Cool and Heat Setpoints
During installation, the ability to run in stand alone
mode allows deactivation of one of the existing, older
wall-mount units, while keeping the shelter cool with
the other unit still operating. Once the first of the Bard
FUSION-TEC wall-mount units is installed, orphan
mode can be enabled early in the installation—keeping
the climate inside the shelter stable and the installers
comfortable while the remainder of the older equipment
is removed and the remaining Bard FUSION-TEC wall-
mount units and LV1000 controller are installed.
To ensure units will go into stand alone mode,
disconnect the plug marked R-T-/R+T+/GND on the
control board located in the wall-mount unit. Be sure
to reconnect the plug before operating the wall-mount
unit as part of the Bard Free Cooling Unit System.
Additionally, should any or all of the FUSION-TEC
wall-mount units lose communication with the LV1000
controller (such as during maintenance), they will
continue to serve the shelter's needs until a repair can
be made.
NOTE: Screenshots shown in this manual reflect
default settings (when applicable).