Verify Units Are Online; Clear Controller Alarm Logs; Complete Installation; Entering Total Number Of Units - Bard Fusion-Tec Installation Instructions Manual

Hide thumbs Also See for Fusion-Tec:
Table of Contents

Advertisement

Fan settings can also be found in the
LV1000 Service Instructions.
8) Press the ESCAPE key several times to return
to Main Menu screen.
FIGURE 45

Entering Total Number of Units

7. Verify Units Are Online

Once a unit is uniquely addressed, communication
can be verified at the LV controller.
With the correct number of units set at the LV
controller, each unit can be remotely viewed from
the controller information screen.
To view these screens:
1) Press ESCAPE key to view the Status screen.
(May need to be pressed more than once.)
2) Press UP or DOWN key until the Quick Menu in
the lower right corner of the screen displays the
Information icon (
3) Press UP or DOWN keys to scroll through the
Information screens until the desired unit
Information screen appears (see Figure 46).
Three Info screens are available for each unit.
Unit serial number and model number and 24-
hour run time information can also be viewed
on these screens.
In addition to being able to remotely view the units,
an alarm will be generated on the LV controller for
units not communicating.
FIGURE 46

Verifying Units

); press ENTER key.

8. Clear Controller Alarm Logs

To clear the LV controller alarm logs:
1) Press MENU key to go to the Main Menu
screen.
2) Use UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to Settings;
press ENTER key.
4) Press UP or DOWN keys to scroll to
Initialization; press ENTER key.
5) Press ENTER key to scroll to Delete Alarm
Logs? (see Figure 47).
6) Press UP or DOWN key to value to YES; press
ENTER key.
7) Press ESCAPE key several times to return to
Main Menu screen.
FIGURE 47

Clearing LV1000 Alarm Logs

9. Complete Installation

Once all the installation steps have been
completed, all alarms and alarm logs have been
cleared and system verification and run test results
were satisfactory, the installation can now be
considered "complete".
Additional programming information can be found
in FUSION-TEC Service Instructions 2100-670
and LV1000 Service Instructions 2100-673.
Manual 2100-674A