APPENDICES

Appendix 2.2 Special Registers

Special registers are data registers of which applications have been determined inside the
PC. Therefore, do not write data to the special registers in the program (except the ones
with numbers marked 2 in the table).
Number
Name
D9000
Fuse blow
D9001
Fuse blow
I/O module
D9002
verify error
Table App2.2 Special Register List
Description
• When fuse blown modules are detected, the lowest
number of detected units is stored in hexadecimal.
(Example: When fuses of Y50 to 6F output modules
have blown, "50" is stored in hexadecimal) To monitor
Fuse blow module
the number by peripheral devices, perform monitor
number
operation given in hexadecimal.
(Cleared when all contents of D9100 to D9107 are
reset to 0.)
• Fuse blow check is executed also to the output
modules of remote I/O stations.
• Stores the module numbers corresponding to setting
switch numbers or base slot numbers when fuse blow
occurred.
I/O Module for A0J2
Setting
Switch
Fuse blow module
number
• In case of remote I/O station, (module I/O number/10H)
+ 1 is stored.
• If an I/O module whose data is different from the
entered data when the power is turned on is detected,
the head I/O number of the detected module is stored
in hexadecimal. When the situation is detected in
multiple modules, the lowest number among the
module will be stored. (Storing method is the same as
that of D9000.) To monitor the number by peripheral
devices, perform monitor operation given in
hexadecimal.
(Cleared when all contents of D9116 to D9123 are
I/O module verify
reset to 0.)
error unit number
• I/O module verify check is executed also to the
modules of remote I/O terminals.
• If an I/O module, of which data is different from data
entered, is detected when the power in turned on, the
I/O number corresponding to the setting switch No. or
base unit No. is stored.(Storing method is the same as
that of D9001).
• In case of remote I/O station, (module I/O number/10H)
+ 1 is stored.
Details
Extension Base Unit
Base Unit
Stored Data
Slot No.
0
1
0
1
2
1
2
3
2
3
4
3
4
5
5
6
6
7
7
8
APP - 20
Applicable CPU
Unusable with
A0J2H.
Only remote
I/O station
information
is valid for
A2C.
Stored Data
5
6
Dedicated to
7
A0J2H.
8
Unusable with
A0J2H.
Only remote
I/O station
information
is valid for
A2C.
Dedicated to
A0J2H.