8.
LOADING AND INSTALLATION
8.4.2

Installation

Installation location of the main base unit and the extension base unit is shown below.
Duct (Height of
50mm (1.97inch)
Extension base unit
(A1S5
B(S1),
A1S6
B(S1))
Panel, etc.
Programmable
controller
Contactor
relay, etc.
100mm (3.94 inch) or more
Figure8.3 Distance between the front
face of the programmable
controller and other devices
Main base
Figure8.1 Parallel installation
panel's ceiling, wiring duct, or
components.
Main base
30mm (1.18inch) or more
30mm (1.18inch) or more
30mm (1.18inch) or more
30mm (1.18inch) or more
Figure8.2 Series installation
Door
Figure8.4 Vertical installation (not allowed)
Indicates the location of ceiling of
the panel, wiring duct or other part.
30mm (1.18inch)
or more
Extension base
30mm (1.18inch)
or more
Duct (Height of
50mm (1.97inch)
or less)
(A5
8 - 10
30mm
Main base
(1.18inch) or more
30mm
(1.18inch) or more
80mm
(3.15inch) or more
Extension base unit
80mm
(3.15inch) or more
B(S1), A1S
B(S1))
Figure8.5 Horizontal installation