Mitsubishi A1SJH(S8) User Manual page 163

Hide thumbs Also See for A1SJH(S8):
Table of Contents

Advertisement

11.
TROUBLESHOOTING
Error
Error Message
Code
(D9008)
"ROM ERR"
17
(Checked at
power-on.)
"RAM ERROR"
20
(Checked at
power-on.)
"OPE. CIRCUIT
21
ERR"
(Checked at
power-on.)
"WDT ERROR"
22
(Checked at
END
instruction.)
"END NOT
24
EXECUTE"
(Checked at
END
processing.)
"WDT ERROR"
25
"UNIT
31
VERIFY ERR."
Table 11.1 AnSHCPU Error Code List (Continue)
Detailed
CPU
Error
module
Code
status
(D9092)
Stop
Parameters and/or sequence programs
are not correctly written to the mounted
memory cassette.
Parameters stored in the memory
cassette have exceeded the limit of
available program capacity.
Ex.) Default parameters (program
capacity: 6k steps) are written to
A1NMCA-2KE.
Stop
The CPU has checked if write and read
operations can be performed properly to
the data memory area of CPU, and as a
result, either or both has not been
performed.
Stop
The operation circuit, which performs
the sequence processing in the CPU,
does not operate properly.
Stop
Scan time exceeds watch dog error
monitor time.
(1) Scan time of user program has been
exceeded for some conditions.
(2) Scan time has increased due to
instantaneous power failure which
occurred during scan.
Stop
(1) AnSHCPU has read other instruction
code due to noise at the
instruction execution.
(2) The
another instruction code for some
reason.
Stop
The
loop in execution of the sequence pro-
gram to disable execution of the
instruction.
Stop
I/O module data are different from those
(Continue)
at power-on.
(1) The I/O module (including the spe-
cial function module) is incorrectly
loaded or has been removed, or a
different unit has been loaded.
Error and Cause
END
instruction has changed to
END
instruction or the like causes a
CJ
END
11 - 14
Corrective Action
(1) Correctly write parameters and/or
sequence programs to the memory
cassette.
(2) Remove the memory cassettes that
contain no parameters or sequence
programs.
(1) Adjust the program capacity for
parameters to the memory cassette
used.
(2) Use the memory cassette of which
memory capacity is larger than the
program capacity for parameters.
Since this is CPU hardware error,
consult Mitsubishi representative.
(1) Calculate and check the scan time of
user program and reduce the scan
time using the CJ instruction or the
like.
(2) Monitor the content of special regis-
ter D9005 by use of peripheral
equipment. When the content is
other than 0, line voltage is insuffi-
cient. When the content is other than
0, the power voltage is unstable.
Reset and run the CPU module again. If
the same error persists again, it is the
CPU hardware error, consult Mitsubishi
representative.
Check the program for an endless loop
and correct.
(1) The bit in special registers D9116 to
D9123 corresponding to the module
causing the verification error is "1."
Use a peripheral device to monitor
the registers to locate the "1" bit, and
check or replace the corresponding
module.
(2) To accept the current module
arrangement, operate the RUN/
STOP key switch to reset.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

A1shA2shcpu (s1)

Table of Contents