Mitsubishi A1SJH(S8) User Manual page 55

Hide thumbs Also See for A1SJH(S8):
Table of Contents

Advertisement

4.
CPU MODULE
Item
Comment
Switch output mode from STOP to RUN
Self-diagnostics function
Operation mode when there is an error
Start-up method at RUN
Latch (power failure compensation) range
Remote RUN/PAUSE contacts
Print title regisration
Keyword registration
I/O assignment
Step operation
Interrupt processing
Data link
Clock function
Allowable momentary power failure period
5VDC internal current consumption
Weight
External dimensions
Performance specifications (Continued)
A1SJHCPU(S8)
Max. 3648 points (Set by the unit of 64 points)
Select "Set the output status at STOP to RUN.
(Default)" or "Output after operation exectution."
Watchdog error supervision (watchdog timer: set within 10ms to 200ms)
Error detection in the memory, CPU, I/O, battery, etc.
Select STOP or continue
(upon power supply on/power restoration after power failure,
automatic restart by turning the RUN switch of the CPU or ON.)
L1000 to L2047 (Default)
(Possible to setup latch ranges for L, B, T, C, D, W)
Possible to set one contact point for each of RUN/PAUSE from X0 to X1FF.
YES (128 characters)
Possible to register number of occupied I/O points and module model names.
Possible to operate an interrupt program by the interrupt module
or constant period interrupt signal.
MELSECNET, MELSECNET/B
Year, month, day, hour, minute, second, day of the week
(automatic detection of the leap year)
-3.1 to +5.3s (TYP.+1.7s)/d at 0
Accuracy
-1.6 to +5.3s (TYP.+2.4s)/d at 25
-9.6 to +3.6s (TYP.-2.1s)/d at 55
Depending on the power supply modules
0.3A
A1SJHCPU:1.00kg
A1SJHCPU-S8:1.06kg
A1SJHCPU:
130mm
(5.12inch) 330mm (13
inch) 82mm (3.23inch)
130mm (5.12inch) 54.5mm (2.15inch) 93.6mm
A1SJHCPU-S8:
130mm
(5.12inch) 435mm
(17.1inch) 82mm
(3.23inch)
4 - 3
Model
A1SHCPU
A2SHCPU(S1)
Initial start
YES
None
0.4A
0.33kg
(3.69inch)
Remark
Set in parameters.
Set in parameters.
Refer to Section 4.1.4
for details.
Set in parameters.
(Refer to Section 4.2.1)
Range set by
parameters.
Set in parameters.
Set in parameters.
Set in parameters.
Refer to Section 5.1.