Mitsubishi A1SJH(S8) User Manual page 171

Hide thumbs Also See for A1SJH(S8):
Table of Contents

Advertisement

11.
TROUBLESHOOTING
Table 11.3 Faults with the output circuit and the corrective actions (Continued)
Situation
The load which
was turned
OFF is turned
Example
ON for a
6
moment at
power-off.
(Transistor
output)
Cause
The load [2] which was turned OFF may be turned ON due to
back electromotive force at the time of power-off [1] if an
inductive load is used.
Output module,
ombined module
Source output
ON
OFF
Output module,
ombined module
Sink output
ON
OFF
[3]
Back electromotive
force
Load
TB1 ON
[2]
TB2 OFF
Load
[1]
Shut off
COM+
CTL-
[3]
Back electromotive
force
Load
TB1 ON
[2]
TB2 OFF
Load
[1]
Shut off
COM-
CTL+
11 - 22
Countermeasure
To prevent the generation of the back
electromotive force, connect diode in
parallel with load where the back
electromotive force has been generated.
Source output
[3]
Back electromotive
force
Load
Sink output
[3]
Back electromotive
force
Load