Output Configuration ("Out.cnf") And A To D Rate ("Ad.rate") - Omega DP41-B Series User Manual

Universal input
Hide thumbs Also See for DP41-B Series:
Table of Contents

Advertisement

10. Data Format Commands (P, G, R, W)

10.9 OUTPUT CONFIGURATION ("OUt.CNF") and A to D RATE ("Ad.RAtE")

BIT POSITION
7
6
5
4
0
1
0
0
0
0
0
1
0
1
0
0
1
1
1
0
0
1
0
1
1
1
0
1
1
1
EXAMPLE: Enable Analog Output, which produces a 0-20 mA current source and set
the A to D conversion rate to 2:
The command data is 01000011 BIN. = 43 HEX. Then send *W1643
TABLE 10.9 OUTPUT CONFIGURATION
3
2
1
0
0
1
0
1
0
1
0
1
OUt.CNFand Ad.RAtE
dISABLE Analog Output
ENAbLE Analog Output
0-10 V Output
0-20 mA Output
Parallel BCD dISABL (not used)
Parallel BCD ENAbLE (not used)
BCD Output Display Value (not used)
BCD Output Peak Value (not used)
Standard Print (Desktop) (not used)
Special Printer (Panel Printer) (not used)
0 A to D Convert Rate 0
1 A to D Convert Rate 1
2 A to D Convert Rate 2
3 A to D Convert Rate 3
4 A to D Convert Rate 4
5 A to D Convert Rate 5
(Not Used)
(Not Used)
10-9

Advertisement

Table of Contents
loading

Table of Contents