Isolated 4-20 mA Transmitter Output

OUTPUT
SOURCE
SCALING RANGE 1.000 to 23.000 mA for any display range
CALIBRATION
ANALOG OUT
PROGRAMMING
ACCURACY
TEMPERATURE
DRIFT
ISOLATED
TRANSMITTER
POWER SUPPLY
EXTERNAL LOOP
POWER SUPPLY
OUTPUT LOOP
RESISTANCE
1.
Automatic reset only (non-latching), when the input
passes the reset point.
2.
Automatic + manual reset at any time (non-latching)
3.
Manual reset only, at any time (latching)
4.
Manual reset only after alarm condition has cleared
(latching)
Note: Front panel button or digital input may be assigned to
acknowledge relays programmed for manual reset.
0 to 999.9 seconds, on & off relay time delays
Programmable and independent for each relay
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
When power is applied to the meter, relays will reflect the
state of the input to the meter.
Process variable (PV), max, min, set points 1-8, Modbus
input, or manual control mode
Factory calibrated: 4.000 to 20.000 = 4-20 mA output
23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and break
± 0.1% of span ± 0.004 mA
0.4 µA/C max from 0 to 65C ambient,
0.8 µA/C max from -40 to 0C ambient
Note: Analog output drift is separate from input drift.
Terminals I+ & R: 24 VDC  10%. May be used to power the
4-20 mA output or other devices. Refer to Figure 5 on page
19 and Figure 16 on page 25.
All models rated @ 40 mA max.
35 VDC maximum
Power supply
24 VDC
35 VDC (external)
Minimum
10 
100 
13
Instruction Manual
Maximum
700 
1200 