Omega DP41-B Series User Manual page 85

Universal input
Hide thumbs Also See for DP41-B Series:
Table of Contents

Advertisement

Note: the Universal Input Meters support only Read Single Register, so the
number of registers should always set to 1.
Screenshot for following examples 1- 3:
Figure 8.1: Read Command Samples via Infinity Configuration Software.
Example 1: For one byte data registers: 1
shown on the Figure 8.1:
01 03 0010 0001 85CF : is to read INPUT CONFIGURATION ( INF.CNF and INPUt ).
FUNCTION
DEVICE
ADDRESS
03 or 04
01
01 03 02 0000 B844 : 1
responded to the 1
DEVICE
ADDRESS
01
For detail description of the VALUES OF THE REGISTER above, refer to Table 10.2 of
Communication Manual.
CODE
STARTING REGISTER
03
00
st
Command Response on Figure 8.1 which device
st
read command.
FUNCTION
NUMBER OF
CODE
BYTES
03
st
data string of Command sent section as
DATA
NUMBER OF REGISTERS
10
00
VALUES OF
REGISTERS
(1 Byte)
00
02
(N/A)
M - 6
CRC
01
85
CRC
20
B9
CF
9C