10.6 ALARM (SETPOINTS 3 AND 4) CONFIGURATION ("AL.CNF")

BIT POSITION
7
6
5
4
0
1
0
1
0
1
0
1
EXAMPLE: To enable Alarm 1 & 2 and setup Alarm1 to activate above Alarm 1 value,
Relay at normal open and use of filtered input value. However, set Alarm 2 to activate
below Alarm 2 value, Relay at normal close, use of unfiltered input value and Alarm
reset disabled at pin#11 of rear terminal P2:
The command data is 10011100 BIN. = 9C HEX. Then send *W119C
TABLE 10.6 ALARM CONFIGURATION
AL.CNF
3
2
1
0
0
AbOVE AL1 Active Above
1
bELOW AL1 Active Below
0
N.OPEN AL1 Normal Open
1
N.CLOSE AL1 Normal Close
0
AL1 Use Un-Filtered Value
1
AL1 Use Filtered Value
0
AbOVE AL2 ACTIVE Above
1
bELOW AL2 ACTIVE Below
N.OPEN AL2 Normal Open
N.CLOSE AL2 Normal Close
AL2 Use Un-Filtered Value
AL2 Use Filtered Value
AL1 & AL2 Enable
AL1 & AL2 Disable
ALARM RESET Enable AT P2-11
ALARM RESET Disable AT P2-11