GE 350 Communications Manual page 96

Feeder protection and control
Hide thumbs Also See for 350:
Table of Contents

Advertisement

SR3 GOOSE CONFIGURATION VIA THE IEC 61850 CONFIGURATOR
4–26
1.9.
Repeat for the second SR3 relay.
1.10. Select OK to save the settings and return to the Main Menu.
- Before we can configure the relay using the IEC61850 Device Configuration tool we
must set the GOOSE message transmission of both relays to Advanced as follows:
1.11. For relay 228, open Setpoints > Communications > GOOSE Configuration >
Transmission.
1.12. Set the GOOSE Type to Advanced.
1.13. Select Save.
1.14. Repeat for Relay 254.
CHAPTER 4: SR3 IEC61850 GOOSE
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE