SR3 GOOSE CONFIGURATION VIA THE IEC 61850 CONFIGURATOR
Configuration lab
steps
4–24
4.
Testing
1.
Configure both relays into the SR3 software and set the GOOSE transmission of
both relays to Advanced.
Configure both SR3 relays into the SR3 software application using the following
procedure
1.1.
Launch the SR3 software and select Device Setup.
1.2.
Select Add Site.
1.3.
Enter an optional site name.
1.4.
Select Add Device.
CHAPTER 4: SR3 IEC61850 GOOSE
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE