Logical Nodes For Metering And Measurement (Ln Group: M) - GE 350 Communications Manual

Feeder protection and control
Hide thumbs Also See for 350:
Table of Contents

Advertisement

CHAPTER 4: SR3 IEC61850 GOOSE

Logical Nodes for metering and measurement (LN Group: M)

350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
Data
Common Logical Node Information
Mod
INC_0
Beh
INS_0
Health
INS_1
NamPlt
LPL_1
Status information
Ind1
SPS_0
Ind2
SPS_0
..
..
Ind32
SPS_0
Table 4-32: MMXU (Measurement)
MMXU class
Attribute Name
Attr.
Type
MMXU
Data
Common Logical Node Information
Mod
INC_0
Beh
INS_0
Health
INS_1
NamPlt
LPL_1
Measured values
TotW
MV_0
TotVAr
MV_0
TotVA
MV_0
TotPF
MV_0
Hz
MV_0
PPV
DEL_0
PhV
WYE_0
A
WYE_1
AuxV
CMV_0
Table 4-33: MSQI (Sequence and imbalance)
MSQI class
Attribute Name
Attr. Type Explanation
MSQI
Data
Common Logical Node Information
Mod
INC_0
Beh
INS_0
Health
INS_1
NamPlt
LPL_1
Mode
Behaviour
Health
Name plate
General Indication
( binary input )
General Indication
( binary input )
..
General Indication
( binary input )
Explanation
Measurement
Mode
Behaviour
Health
Name plate
Total active power (P)
Total reactive power (Q)
Total apparent power (S)
Average power factor (PF)
Line Frequency
Phase to phase voltages (VL1L2,...)
Phase to ground voltages (VL1ER, ...) O
Phase currents (IL1, ...)
Phase to ground voltages (VL1ER, ...) O
Measurement
Mode
Behaviour
Health
Name plate
IEC 61850 LOGICAL NODES
M
M
M
M
O
Remote Input 1
O
Remote Input 2
..
..
O
Remote Input 32
M/O Notes
M
M
M
M
O
Real Power
O
Reactive Power
O
Apparent Power
O
Power Factor
O
VLFREC
O
Phase Voltage
Ground Voltage
O
Currents
Vaux
M/O Notes
M
M
M
M
4–59

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents