IEC 60870-5-103 SERIAL COMMUNICATION

103 general settings

2–24
Number
Comms Port
Slave Address
Synchronization Timeout
If Comms Port is set to NONE, the IEC 870-5-103 communication protocol will not be
available.
If the user sets a value other than 0 in the Synchronization Timeout setting, when this time
expires without receiving a synchronization message, the Invalid bit will be set in the time
stamp of a time-tagged message.
It is necessary to configure other port settings: Baud Rate, etc.
CHAPTER 2: RS485 INTERFACE
Value
COM1
1
30 min
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
Range
Enum[None,Com1]
[0..254]
[0..1440]min