CHAPTER 4: SR3 IEC61850 GOOSE
NOTE:
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
To configure Relay228_GOOSE7 to transmit Virtual Input 1 proceed as follows:
In the Transmission Device column expand the tree of 228_GOOSE7 such that
Virtual input 1 is displayed. Left mouse click on Virtual Input 1 in the
Transmission Device column and drag this point into the relay(s) that are to
receive the status of this point. In our example we would left mouse click onto
Virtual Input 1 and drag it into the Reception column corresponding to the relay
labeled 230_GOOSE7. In this case we dragged Virtual Input 1 from the relay
labeled 228_GOOSE7 into the first row of relay 230_GOOSE7. This position
corresponds to Remote Input 1. This is the process that is used to configured both
the transmission and reception. Once the configuration is complete the users
must select SAVE. Upon a SAVE selection, the SGC program will take the
information within the screen and determine how to set up the transmission and
reception list for each device.
The simplified GOOSE Configuration Tool required all settings files to be present before
launching the tool. If at a later date settings files need to be added or removed, the
above process must be repeated from the beginning.
Before the final step of downloading the settings to each relay we need to enable the
Virtual Input within 228_GOOSE7 such that we can change its status.