CHAPTER 3: ETHERNET INTERFACE
NOTE:
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
SETTINGS
DNP Client Address 5
DNP TCP/UDP Port Number
DNP Unsol Resp Function
DNP Unsol Resp Timeout
DNP Unsol Resp Max Retries
DNP Unsol Resp Dest Addr
DNP Time Sync IIN Period
DNP Message Fragment Size
DNP Object 1 Default Variation
DNP Object 2 Default Variation
DNP Object 20 Default Variation
DNP Object 21 Default Variation
DNP Object 22 Default Variation
DNP Object 23 Default Variation
DNP Object 30 Default Variation
DNP Object 32 Default Variation
DNP TCP Connection Timeout
The setting DNP Unsolicited Response Timeout affects DNP TCP clients only; not serial
and UDP clients. Possible values that can be selected for this setting lie between 0 and 60
seconds.
In addition to this selected timeout, up to an additional 10 seconds is required to send
the response packet.
Table 3-2: DNP point list
SETTINGS
Binary Input Point 0 Entry
Binary Input Point 63 Entry
Analog Input Point 0 Entry
Analog Input Point 0 Scale Factor 1
Analog Input Point 0 Deadband
Analog Input Point 31 Entry
Analog Input Point 31 Scale
Factor
Analog Input Point 31 Deadband
Binary Output Point 0 ON
Binary Output Point 0 OFF
DNP ETHERNET PROTOCOL SETTINGS
PARAMETER
RANGE
0. 0. 0. 0
20000
0 to 65535
Disabled
Disabled ; Enabled
5 s
0 to 60 s
10
1 to 255
1
0 to 65519
1440 min
1 to 10080 min
240
30 to 2048
2
1 ; 2
2
1 ; 2
1
1 ; 2 , 5 ; 6
1
1 ; 2 ; 9 ; 10
1
1 ; 2 , 5 ; 6
1
1 ; 2 , 5 ; 6
1
1 ; 2 ;3 ; 4
1
1 ; 2 ;3 ; 4
120 s
10 to 300 s
PARAMETER
RANGE
Select entry
Operands
from a list
Select entry
Operands
from a list
Select entry
Analog parameters
from a list
0.001 ; 0.01 ; 0.1 ; 1 ; 10 ; 100 ;
1000 ; 10000 ; 100000
30000
0 to 100000000
Select entry
Analog parameters
from a list
1
0.001 ; 0.01 ; 0.1 ; 1 ; 10 ; 100 ;
1000 ; 10000 ; 100000
30000
0 to 100000000
Select entry
Virtual Input 1 to 32 and Force
from a list
Coils
Select entry
Virtual Input 1 to 32 and Force
from a list
Coils
FORMAT
F150
F1
F126
F1
F1
F1
F1
F1
F1
F1
F78
F79
F80
F81
F82
F83
F1
FORMAT
F134
F134
F85
F9
F85
F9
F86
F86
3–23