Modbus User Map - GE 350 Communications Manual

Feeder protection and control
Hide thumbs Also See for 350:
Table of Contents

Advertisement

GE
Digital Energy
SR350 Feeder Protection System
Chapter 10: Using the MODBUS User
Map

MODBUS User Map

350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
Using the MODBUS User Map
350 relay units incorporate a powerful feature called Modbus User Map, that allows the
user to read 125 non-consecutive data records.
A master computer will often have to interrogate continuously several connected slave
relays. If the values being read are "randomly" positioned along the memory map, reading
them may require several transmissions, and this may cause a communications overload.
Data records that are positioned in this manner in the memory map, can be remapped to
the address of an adjacent record in the User Map area, so that they can be accessible to
the master computer with only a single read operation.
To program the map this way, addresses for the required records must be written in the
index area, which is located at the addresses from 40524 (0x020B) to 40648 (0x287).
Only single data from the Actual Values subset can be set in the map. The ranges of
addresses that can be configured in that index area are:
Range1 : 30001 to 30523 (Product Device Code to Internal Fault Cause)
[The address 30302 (Current Security Access Level) cannot be configured.]
Range2 : 30946 to 32036 (Alarm Status 4 to Last Actual Values Register)
The values that correspond to the points provisioned in the User Map index (40524
(0x020B) to 40648 (0x287)) may be read from the Actual Values map area located at the
addresses from 30524 (0x020B) to 30648 (0x0287).
Table 10-1: User Map Settings
MODBUS
Hex
Description
Address
Addres
s
40524
20B
User Map Address 1
40525
20C
User Map Address 2
40526
20D
User Map Address 3
40527
20E
User Map Address 4
40528
20F
User Map Address 5
40529
210
User Map Address 6
40530
211
User Map Address 7
Min
Max
Step
30001
43763
1
30001
43763
1
30001
43763
1
30001
43763
1
30001
43763
1
30001
43763
1
30001
43763
1
Format
Factory
Code
Default
F1
30305
F1
30505
F1
30506
F1
30960
F1
30961
F1
30958
F1
30959
10–1