Measurands - GE 350 Communications Manual

Feeder protection and control
Hide thumbs Also See for 350:
Table of Contents

Advertisement

IEC 60870-5-103 SERIAL COMMUNICATION

Measurands

2–22
Settings
Digital Status
Point 1 Entry
Select entry from list
....
....
Point 64 Entry
Select entry from list
This means that for each digital point 3 settings are required.
Example:
Modbus Address
Description
43879
Point 1 Entry Digital Status
44223
Point 1 Entry Function Type
44224
Point 1 Entry Information Number
The "Point Entry Digital Status" reuses the DNP Binary Input 43029, 43030, ...
Some analog points are supported by the 350 relay, with compatible information number
that have been identified in the device profile.
For the other measurands, it is possible to use the EnerVista SR3 Setup to select the desired
point and assign the Identification Type (3 or 9), Function Type <0..255>, and Information
Number <1..255>.
If the user selects Identification Type 3 (ASDU 3) only four measurands are available for
configuration, but if Identification Type 9 (ASDU 9) is selected, up to nine measurands can
be sent in the IEC103 slave answer. For each measurand, all metering values that the
350 supports, are available in order to be mapped. There are 3 possible configurable
ASDUS.
For example, eDataVab is the index in the Modbus Memory Map.
Modbus Address
Description
44384
First ASDU Identification Type
44385
First ASDU Function Type
44386
First ASDU Information Number
44387
First ASDU Scan Timeout
44388
First ASDU First Analog Entry
44389
First ASDU First Analog Factor
44390
First ASDU First Analog Offset
44391
First ASDU Second Analog Entry
44392
First ASDU Second Analog Factor
44393
First ASDU Second Analog Offset
...
...
44412
First ASDU Ninth Analog Entry
44413
First ASDU Ninth Analog Factor
...
...
44443
Second ASDU Ninth Analogue Entry
44444
Second ASDU Ninth Analogue Factor
44445
Second ASDU Ninth Analogue Offset
...
...
CHAPTER 2: RS485 INTERFACE
Information Number
<0 – 255 >
<0 – 255 >
Value
0x8242 (Undercurrent Trip)
160
144
Value
3 or 9
<0 – 255 >
< 0 – 255 >
< 0 – 1000> secs
Vab
1
0
Ib
1
0
...
Ib
1
...
...
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
Function Type
<0 – 255 >
<0 – 255 >
Format
FC134
F1
F1
Format
F1
F1
F1
F1
F1
F3
F1
F1
F3
F1
...
F1
F3
...
...