Indoor Unit
1.6

Removal of the Fan Rotor / Fan Motor

Procedure
Step
1. Remove the
right side
panel.
1
Loosen the two screws.
Lift the right side panel
2
and remove it.
2. Remove the fan rotor.
1
Loosen the screw and
remove the
fan motor
fixture.
2
Loosen the fixing screw
of the fan rotor.
168
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Si04-306E
Points
You can remove the fan
rotor without detaching the
right side panel.