Removal of Fan Motor

4. Removal of Fan Motor
Procedure
Step
1
Remove the nut and
remove the outdoor fan.
2
Remove the 2 screws of
the fan motor mount.
3
Disconnect the for motor
lead wire by releasing the
2 clamps fixing the wire.
Remove the 4 screws to
remove the fan motor.
10
Warning Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Fan
motor
mount
(Backside)
Fan motor
Preparation
(R10362)
(R10363)
Clamp
(R5567)
Si12-793
Points
Disconnect the connector for
the fan motor.
Nut size : M6
10 mm
(R12236)
When reassembling, align
the
mark of the outdoor
fan with the D-cut section of
the motor shaft.
When reassembling, fix the
fan motor lead wire to the
clamps to avoid contact with
the outdoor fan.
(R5568)