Function of Main Structural Parts

2. Function of Main Structural Parts

2.1

Function of Thermistor

2.1.1 Heat Pump Model
A
Outdoor Heat
1. The outdoor heat exchanger thermistor is used for controlling target discharge temperature.
Exchanger
Thermistor
2. The outdoor heat exchanger thermistor is used for detecting the discharge thermistor
3. The outdoor heat exchanger thermistor is used for high pressure protection during cooling
B
Discharge
1. The discharge pipe thermistor is used to control the discharge pipe.
Pipe Thermistor
2. The discharge pipe thermistor is used for detecting the discharge thermistor disconnected.
C
Indoor Heat
1. The indoor heat exchanger thermistor is used for controlling target discharge pipe
Exchanger
Thermistor
2. The indoor heat exchanger thermistor is used to prevent freezing.
3. During heating: the indoor heat exchanger thermistor is used for detecting the discharge
58
A
Four way valve
B
Set a target discharge temperature depending on the outdoor and indoor heat exchanger
temperature.
Control the electronic expansion valve opening so that the target discharge temperature can
be obtained.
disconnected when cooling.
When the temperature of the discharge piping is lower than the temperature of outdoor heat
exchanger, a disconnected discharge thermistor can be detected.
operation.
If the temperature of discharge pipe (used in place of the inner temperature of the
compressor) rises abnormally, the operating frequency drops or the operation must be
halted.
temperature.
Set a target discharge pipe temperature according to the outdoor and indoor heat exchanger
temperature.
Control the electronic expansion valve so that the target discharge pipe temperature can be
obtained.
During the cooling operation, if the temperature drops abnormally, the operating frequency
becomes lower, then the operation must be halted.
pipe thermistor disconnected.
When the discharge pipe temperature become lower than an indoor heat exchanger
temperature, a disconnected discharge pipe thermistor can be detected.
The indoor heat exchanger thermistor is also used for preventing abnormal high pressure.
Electrontic
expansion valve
Compressor
Si04-306E
C
(R5318)
Function and Control