Installation
Manual
Power Wiring
Interconnections
All wiring must be the proper size, properly supported, of
approved insulative qualities, and protected by NEC
approved conduit Use flexible conduit between the
enclosure and any rigid conduit
_
AUTION!
Per NEC code, power voltage leads
must be run in separate conduit from Low voltage
transfer switch "signal" leads.
Complete the following connections between the
generator, transfer switch and main distribution panel
(Figure 14).
I.
Connect utility power supply leadsfrom a two pole
breaker installed in the main distribution panel to
transfer switch terminals marked "UTILITY
CONNECTION".
Use a 50 Amp circuit breaker.
Ensure breaker is turned OFE
2.
Connect
utility neutral to the transfer switch
"NEUTRAL"
bus.
3.
Connect
utility ground to the transfer switch"GND"
bus.
4.
Connect generator
power supply leads from the
generator's
control
panel to transfer switch terminals
marked "GENERATOR
CONNECTION".
5.
6.
7.
Connect generator Neutral from the control panel to
the transfer switch NEUTRAL bus.
Connect generator GND from the control panel to
the transfer switch GND bus.
Torque all wire connections/fasteners
to values
recommended
in Figure 15.
Main
Diagnostic
LED
Distribution
/
Panel
r-_]
Bus
I
Dual Pole
Breaker
Ground
P, u s
Utility
Connection
Automatic
Power Transfer Switch
"i _ j _
Neutral
Bus
Home Generator
Rear of
System
Control
Generator
Panel
Generator
Neutral
is
White
wire
Control
Signal
Connections
/