• Install flexible gaseous pipe (supplied) between the Home
Generator
System Fuel Inlet port and rigid piping.
CAUTION!
Connector
is not to be installed
underground
or in contact with the ground.
_k
CAUTION!
Entire flex connector
must be visible
for periodic inspection and must not be concealed
within, contact, or run through any wall, floor, or
partition.
• Piping must be of the correct size to maintain the
required
supply pressures and volume flow under varying
conditions.
• Use an approved pipe sealant or joint compound on all
threaded
fittings to reduce the possibility of leakage.
• Installed piping must be properly purged and leak tested,
in accordance with applicable codes and standards.
Consider
the following
factors when planning
to
install the fuel supply system:
The Home Generator
System engine is fitted with a fuel
carburetion
system that meets the specifications of the
California Air Resources Board for "tamper-proof"
dual fuel
systems.The
unit will run on natural gas or liquefied
propane.
• A minimum of one manual shutoff valve should be placed
in-line and located outside the building to facilitate
servicing the generator.
• Natural gas fuel supply pressure at the generator's
fuel
inlet port should be between 5 to 7 inches of water (in.
W.C.) at full load. LP fuel supply pressure should be I I to
14 inches of water
(in.W.C.)
at full load.
The Home
Generator
System
unit has been factory
set to run
on natural
gas. If you need to change from
natural gas to LP gas, the unit will need to be reconfigured,
as described on page 18.
It is recommended
that the fuel connection incorporate
the following components:
• A manual fuel shut-off valve located outside the building,
just before the generator unit.
• The termination of hard piping should include a sediment
trap.
• A manometer port should be provided.
The manometer port permits temporary installation of a
manometer (Figure 6), to ensure that the engine receives
the correct fuel pressure to operate efficiently throughout
its operating range.
When the initial test runs are completed, the manometer is
removed and the port is plugged.A typical final fuel
connection assembly is shown in Figure 7.