Three-Phase 400 V Class Drive Models 4A0005 To 4A0027 - YASKAWA Z1000 User Manual

Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

A.1 Power Ratings
u

Three-Phase 400 V Class Drive Models 4A0005 to 4A0027

CIMR-Zo4A
Input Voltage
Maximum
460 V or higher
Applicable
Motor
Input Voltage
Capacity
lower than 460 V
Input Current (A)
Input
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
Minimum Power Supply Capacity (kVA)
Rated Output Capacity
(kVA)
Rated Output Current (A)
Output
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
Harmonics
Reduction
EMC
Filter (IEC/EN 61800-3 Category 2)
<1> The motor capacity (HP) refers to an NEC Table 430.250 208 V motor. The rated output current of the drive output amps should be equal to or
greater than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> The motor capacity (HP) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the
motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<3> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<4> Rated motor capacity is calculated with a rated output voltage of 460 V.
<5> Rated motor capacity is calculated with a rated output voltage of 400 V.
<6> Carrier frequency is set to 5 kHz. Current derating is required to raise the carrier frequency.
270
Table A.3 Power Ratings (Three-Phase 400 V Class)
Item
HP
<1>
kW
HP
<2>
kW
<3>
Rated Voltage
Rated Frequency
Input Voltage
460 V or higher
Input Voltage
lower than 460 V
Overload Tolerance
Carrier Frequency
DC Link Choke
0005
0008
3
5
2.2
3.7
2
4
1.5
3.0
4.8
7.6
Three-phase 380 to 480 Vac 50/60 Hz / 510 to 680 Vdc
4
7
3.8
6.1
<4>
3.3
5.3
<5>
4.8
7.6
<6>
<6>
110% of rated output current for 60 s
140% of rated output current for 0.5 s
User adjustable between 1 and 12.5 kHz
(Maximum Frequency varies with Rated Output Capacity)
Three-phase 380 to 480 V (proportional to input voltage)
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
Specification
0011
0014
0021
7.5
10
15
5.5
7.5
11
5
7.5
10
4.0
5.5
7.5
11
14
21
-15 to 10%
±5%
10
12
18
8.8
11
17
7.6
9.7
14.5
11
14
21
<6>
<6>
<6>
240 Hz
Built-in
Built-in
0027
20
15
15
11
27
23
22
18.7
27
<6>

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents