VISTA-128BP/VISTA-250BP Installation and Setup Guide
Zones 988 and 990 are used to supervise the RF
reception of receivers 2 and 1, respectively. The
reception is supervised for two conditions:
1.
The receiver goes "deaf" (doesn't hear from
any transmitter) within a programmed
interval of time (defined by program field
1*30).
2.
Proper RF reception is impeded (i.e., jamming
or other RF interference). The control checks
for this condition every 45 seconds.
A response type (05 Day/Night) must be
U L
programmed for zones 990 (1
nd
988 (2
receiver) for UL installations.
The 5881ENHC receiver contains front and back
tampers that permit its use in commercial
burglary installations.
You may only mount the 5881ENHC its own
plastic housing. Otherwise, the receiver constantly
reports a tamper condition.
The control checks the receiver connections about
every 45 seconds. The receiver supervisory zone is
8 + 2-digit receiver device address (for example,
Device address 05 = supervisory zone 805).
NOTE: This zone must be programmed with a
response type (e.g., type 05 Day/Night Trouble)
before it supervise the connection to the receiver.
Use two identical receivers to provide either a
greater area of coverage or redundant protection.
They must be set for different addresses.
Any zone from 1 to 250 can be used as a 5800
Series wireless zone, with the exception of zone 64
(reserved for a wireless keypad).
RF System Installation Advisories
Place the receiver in a high, centrally located area.
Do not place it on or near metal objects. This will
decrease the range and/or block transmissions.
Install the RF receiver at least 10 feet from the
control panel or any keypads, to avoid interference
from the microprocessors in these units.
If dual receivers are used:
a.
They must be at least 10 feet from each other,
as well as from the control panel and remote
keypads.
b.
Each receiver must be set to a different device
address. The receiver set to the lower address
is considered the 1
supervisory purposes.
c.
The House IDs must be the same.
d.
Using two receivers does not increase the
number of transmitters the system can
support (249 zones using the 5881H, plus a
wireless keypad).
3-14
WWW.DIYALARMFORUM.COM
st
receiver) and
st
RF receiver for
WWW.DIYALARMFORUM.COM
Installation and Setup of 5881 RF Receivers
Take note of the address you select for the RF
receiver, as this address must be enabled in
the system's Device Programming in the #93
Menu Mode .
Figure 3-19: Installing the 5881ENHC with Tamper
Protection
To install the 5881 RF receiver, perform the following
steps:
Step
Action
1
Mount the receiver, following the advisories
stated previously.
2
Set the DIP switches in the receiver for the
address (01-07). See Figure 3-20.
Make sure the address setting is not
being used by another device (keypad,
relay module, etc.).
3
If installing a 5881ENHC, install a flat-head
screw (supplied) in the case tamper tab as
shown in Figure 3-19. When the receiver is
pried from the wall, the tamper tab will
break off and remain on the wall. This will
activate a tamper switch in the receiver and
cause generation of a tamper signal. Note
that this signal will also be generated when
the receiver's front cover is removed.
4
Connect the receiver's wire harness to the
keypad terminals (6, 7, 8, and 9). Plug the
connector at the other end of the harness
into the receiver.
5
Refer to the Installation Instructions
provided with the receiver for installations
regarding antenna mounting, etc.
SCREW