Trouble Conditions

Check or Trouble Messages
Display
Description
CHECK or
This indicates that a problem exists on
TRBL
the zone number displayed. Zone
trouble may be caused by one of the
(as per field
following conditions:
1✳07)
A hardwired fire zone is open
(broken wire).
A Day/Night zone (zone type 5) is
faulted.
A polling loop zone is not seen by
the control panel.
A polling loop zone has been
tampered (cover removed on a
4190).
A wireless zone has not checked in
during the time programmed in field
1✳31.
A 5800 Series transmitter has been
tampered (cover removed).
CHECK 6XX
This indicates a trouble on a 4204CF
XX = 01-32
Supervised Bell Output (corresponding
relay number 01-32).
CHECK 8XX
This indicates a trouble on a peripheral
XX = 00-30
device (connected to the panel's keypad
terminals) of the corresponding device
address (00-30).
CHECK 9XX
This indicates that a system trouble
XX = 00-99
exists (RF receiver, bell output, etc.).
If the problem has been corrected, enter an
OFF sequence (Security Code + OFF) twice
to clear the display.

To the Installer

Regular maintenance and inspection (at least
annually) by the installer and frequent testing by the
user are vital to continuous satisfactory operation of
any alarm system.
The installer should assume the responsibility of
developing and offering a regular maintenance
program to the user as well as acquainting the user
with the proper operation and limitations of the alarm
system and its component parts. Recommendations
must be included for a specific program of frequent
testing (at least weekly) to ensure the system's proper
operation at all times.
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Section 10 – Testing The System
Power Failure
Display
Description
AC LOSS
This indicates that the system is
operating on battery power only. Check
POWER
to see that the circuit breaker for the
LED is off
branch circuit that your system's
transformer is wired to has not been
accidentally turned off. Instruct the
user to call a service representative
immediately if AC power cannot be
restored.
Other System Messages
Display
Description
COMM
This indicates that a failure occurred in
FAILURE
the telephone communication portion of
your system.
LO BAT
This indicates that a low-battery
condition exists in the wireless
transmitter displayed. Pressing any key
silences the audible warning sound.
SYSTEM
This indicates that a low-battery
LO BAT
condition exists with the system's
backup battery.
RCVR
This indicates that the system has more
SETUP
wireless zones programmed than the
ERROR
wireless receiver can support. If this is
not corrected, none of the zones in the
system will be protected. If additional
wireless zones are desired, use an
appropriate receiver.
MODEM
This indicates that the control is on-line
COMM
with a remote computer.
Turning the System over to the User
Fully explain the operation of the system to the user
by going over each of its functions, as well as the
User's Manual supplied.
In particular, explain the operation of each zone
(entry/exit, perimeter, interior, fire, etc.). Be sure the
user understands how to operate any emergency
feature(s) programmed into the system.