Ignore Expansion Zone Tamper; Intelligent Test Report; Test Report Interval - Honeywell VISTA-128BP Installation And Setup Manual

Commercial burglary partitioned security systems
Hide thumbs Also See for VISTA-128BP:
Table of Contents

Advertisement

FIELD
TITLE and DATA ENTRIES
VIP Module Phone Code
*20
1-9 = first digit of access code
∗ ∗ ∗ ∗ or # = second digit of access code (enter #
+11 for "∗", or # +12 for "#")
To disable enter 00 for the 1
Prevent Fire Timeout
*21
0 = disable (timeout)
1 = enable (no timeout)
Keypad Panic Enables (partition-
*22
specific)
0 = disable
1 = enable
Multiple Alarms (partition-
*23
specific)
0 = disable
1 = enable

Ignore Expansion Zone Tamper

*24
0 = disable (tamper detection)
1 = enable (no tamper detection)
Burglary Trigger for Response
*25
Type 8
0 = disable
1 = enable

Intelligent Test Report

*26
0 = disable
1 = enable

Test Report Interval

*27
Enter 0001-9999 for the test report interval in
hours.
Enter 0000 for test reporting.
Power-Up in Previous State
*28
0 = disable
1 = enable
Quick Arm (partition-specific)
*29
0 = disable
1 = enable
WWW.DIYALARMFORUM.COM
EXPLANATION
If a 4285/4286 Voice Module is being used, enter the 2-digit phone code used to
access the system.
Must be disabled for UL installations.
st
digit
If enabled, there is no timeout of the alarm sounder duration for all fire zones,
regardless of partition, so that fire sounding continues until the system is reset.
If disabled, (timeout) the normal burglary sounder duration (field ✳13) applies to
fire alarms.
If enabled, the keypad panics (zones 995, 996, and 999) may be used in this
partition. There are 3 entries in this field, one for each panic.
If enabled, allows more than one alarm sounding for a given zone during an
armed period.
NOTE: that multiple alarm soundings will not occur more frequently than
allowed by the programmed alarm sounder duration. This has no impact on the
number of communication messages transmitted.
Must be 1 for UL installations.
If disabled, the system monitors the tampers on expansion zones.
NOTE: Only applicable to certain polling loop sensors with tamper switches or
5800 Series transmitters.
Must be 0 for UL installations.
If enabled, allows triggering of Output 3 (pin 7) of the J7 header to include zone
response type 8 (24-hr. auxiliary).
If enabled, no test report is sent if any other type of report was sent since the
last test report.
If disabled, test reports are sent at the set intervals, regardless of whether or not
any other report has been sent.
Must be 0 for UL applications.
If a test report is desired, enter a test code in Report Code Programming in #93
Menu Mode . Set first test report time in field *83.
Maximum Test report interval is 0024 for UL installations.
If enabled, the system, upon power-up, reverts to its status prior to a complete
power loss.
If disabled, the system always powers up in a disarmed state.
NOTE: Neither authority level 0 nor 5 can be used to disarm the system if the
control powers up armed.
Must be 1 for UL applications.
If enabled, allows arming of the burglary system in AWAY, STAY, INSTANT, or
MAXIMUM mode by using the [#] key instead of the user code.
NOTES:
When armed, the system reports closing as User 0 if Open/Close reporting for
User #2 (typically a Master level user) was enabled for a given partition.
If Quick Arm is used, the Installer Code and Authority Level 5 codes cannot
disarm the system.
WWW.DIYALARMFORUM.COM
Section 5 – Data Field Descriptions
5-3